Honeywell e528 Product Manual page 7

Smart digital thermostat
Hide thumbs Also See for e528:
Table of Contents

Advertisement

E528 Product Guide
Table 3. E528 3G/4G Low Voltage Harness (P/N 62-1467) Pinout
Wire Color
Female
Connector
Brown
1
Red
2
Orange
3
Yellow
4
Green
5
Blue
6
Rev 8.0 12/16/2016
Male
Function
Connector
1
Common
2
12VDC Out/In
3
S5Bus Data Tx/RX or IN 2
4
IN 1
5
CNET B
6
CNET A
External temperature control sensor: This header accepts the wiring
harness from an external temperature probe that can be used to supply the
e528 with remote temperature measurements. The e528 uses a 10K 1%
thermistor for external temperature measurement. This external temperature
sensor can be used to monitor room temperature at a different location from
where the e528 is mounted or to monitor pipe water temperature.
RS485 Networks: (refer to Figure 5)
E528.3G cannot act as the media gateway for in-room traffic towards the
RS485 network. The most common way to connect the e528.3G is to connect
a PC-485.S5 (P/N: 01-9905) on the S5bus.
E528.4G to 2G RS485 Networked Application: with or without door switch
input (See Figure 6)
Using the adapter (P/N 203-251), connect the harness from the wall
box (P/N 62-1462) previously connected to the thermostat being
replaced to H1 of the adapter.
Connect the harness H3 (rainbow) of 203-251 to the low voltage
comm/device connection of the e528.4G
Connect the harness H2 (black) of 203-251 to the RS485 header of the
e528.4G
NOTE: Take care to not reverse the connections to the e528.4G!
Comment
GND
12VDC Supply
Communication Bus
Door, Window, PIR, Other
RS485 Twisted Pair
RS485 Twisted Pair
7

Advertisement

Table of Contents
loading