Caution
Caution
maintenance
Louver edges can be very sharp and could cut skin if proper protec-
tion is not used. Always wear gloves and sleeves when handling
eliminator packs.
To remove the louvers, place both hands on the louver face and push up,
this will indicate where one assembly stops and another starts. Push a single
louver section up until it hits the top of the metal retaining channel (1). Pull
the bottom side of the louver out away from the fluid cooler and remove the
louver (2). Repeat this procedure for other packs to gain necessary access.
Proper louver pack replacement is essential to operation. To ensure packs are
reinstalled in the correct orientation, it is recommended that one pack is left
in its original location inside the fluid cooler as a reminder of pack orientation.
Replace packs in the reverse procedure explained for removal. Place packs
in the fluid cooler in the order they were removed. Packs should nest tightly
with each other, leaving a level surface with no gaps.
Coil Eliminator Removal:
The coil eliminators are comprised of a series of thermoformed PVC pack as-
semblies, oriented to strip water from the air prior to leaving the fluid cooler.
They are packed tightly to ensure no water escapes.
Eliminator edges can be very sharp and could cut skin if proper
protection is not used. Always wear gloves and sleeves when han-
dling eliminator packs.