operation
Protection Against Coil Freezing:
Ethylene and propylene glycol solutions are the best means to protect the
coil from freezing. The following table provides the coil volume for each MH
Fluid Cooler model. MHF7111 and MHF7113 coil volumes are for both coils
added together.
Wet Coil
Model
m
3
MHF7103_ _ _AN
.375
MHF7103_ _ _AF
.375
MHF7103_ _ _BN
.557
MHF7103_ _ _BF
.557
MHF7105_ _ _AN
.500
MHF7105_ _ _AF
.500
MHF7105_ _ _BN
.746
MHF7105_ _ _BF
.746
MHF7105_ _ _CN
.867
Wet Coils
Model
m
3
MHF7111_ _ _AN
2.32
MHF7111_ _ _AF
2.32
MHF7111_ _ _BN
3.35
MHF7111_ _ _BF
3.35
MHF7111_ _ _CN
3.32
MHF7111_ _ _CF
3.32
Copper Coil:
Wet Coils
Model
m
3
MHF7103_ _ _ANC
.265
MHF7103_ _ _BNC
.378
MHF7105_ _ _ANC
.348
MHF7105_ _ _BNC
.507
When the use of industrial antifreeze solutions is not possible, the system
must be operated to meet both of the following conditions.
1. Maintain sufficient flow rate through the coil.
2. Maintain sufficient heat load on the process fluid. Fluid exiting the coil
must be maintained at or above 7°C. Cycling of the recirculation pump
should not be used to control process temperatures.
Dry Coil
Model
m
3
MHF7105_ _ _CF
.110
MHF7107_ _ _AN
MHF7107_ _ _AF
.110
MHF7107_ _ _BN
MHF7107_ _ _BF
.148
MHF7107_ _ _CN
MHF7107_ _ _CF
.148
MHF705_ _ 082
MHF705_ _ 122
Dry Coils
Model
m
3
MHF7113_ _ _AN
.504
MHF7113_ _ _AF
MHF7113_ _ _BN
.504
MHF7113_ _ _BF
MHF7113_ _ _CN
.504
MHF7113_ _ _CF
Dry Coils
Model
m
3
MHF7105_ _ _CNC
MHF7107_ _ _ANC
MHF7107_ _ _BNC
MHF7107_ _ _CNC
Wet Coil
Dry Coil
m
3
m
3
.867
.148
.954
.954
.212
1.43
1.43
.212
1.65
1.65
.212
1.44
2.14
Wet Coils
Dry Coils
m
3
m
3
2.79
2.79
.538
4.05
4.05
.538
4.02
4.02
.538
Wet Coils
Dry Coils
m
3
m
3
.507
.651
.954
.954
19