Marley Fluid Cooler Engineering Data Schematic Support Hoisting Info Noise Attenuator Option Freeze Protection Water Quality Specifications / Base Base Thermal Performance Performance Warranty Coil Design Loading Construction Mechanical Equipment Drift Eliminators Hot Water Distribution System Casing Access Collection Basin Warranty Specifications / Options Stainless Steel Options...
Page 3
Marley Fluid Cooler Air Movement Package ■ Forward-curved centrifugal fans are dynamically balanced and mounted on tubular steel shafts. Fans are supported by roller-bearings mounted at both ends with heavy-guage steel supports. Spherical roller bearings are rated at an L Fan guard / Air-inlet screens are 16 gauge galvanized steel.
Page 4
Marley Fluid Cooler The Marley MC Fluid Cooler is particularly suited to the urban environment, reducing noise while increasing energy efficiency and performance. By keeping the process fluid in a clean, closed loop, and combining the function of a cooling tower and heat exchanger into one system, they provide superior operational and maintenance benefits.
Marley Fluid Cooler 1249 4" INLET 4" OUTLET ACCESS SIDE ELEVATION ALL MODELS 2740 AIR INLET ELEVATION MODELS 7013F081 - 7013J121 Engineering Data : Schematic Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based...
Page 7
Marley Engineering Data : Schematic Fluid Cooler Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based on customer's specific design requirements. 3550 2400 1132...
Page 8
Marley Fluid Cooler Dimensions Model 7054L081 7054M081 7054N081 4172 7054P081 7054Q081 7054L101 7054M101 7054N101 4400 7054P101 7054Q101 7054L121 7054M121 7054N121 4629 7054P121 7054Q121 7055P081 7055Q081 4172 7055R081 7055P101 7055Q101 4400 7055R101 7055P121 7055Q121 4629 7055R121 NOTE 1 Use this bulletin for preliminary layouts only. Obtain current drawings from your Marley sales representative.
Page 9
Marley Engineering Data : Schematic Fluid Cooler Use this data for preliminary layouts only. Obtain current drawing from your Marley sales representative. The UPDATE web-based selection software —available at www.spxcooling.com—provides MC Fluid Cooler model recommendations based on customer's specific design requirements. 2980 2680 1480...
Marley Fluid Cooler C L ANCHOR BOLT HOLES FOR " DIA. ANCHOR BOLTS 4 REQD TOWER COLLECTION BASIN- AIR INLET FACE SUPPORTING STEEL NOTE 1 Use this bulletin for preliminary layouts only. Obtain current drawings from your Marley sales representative for final design.
Marley Fluid Cooler 80° Model 7012 7013 7014 7054 7055 7073 7074 7075 NOTE 1 Hoisting operations can be dangerous and suitable safety precautions should be taken to protect personnel and the equipment being hoisted. 2 All hoisting equipment should be certified and comply with local and national safety regulations.
Marley Fluid Cooler AIR INLET ELEVATION Model Depth 7012 1220 7013 1220 7014 1220 7054 1220 7055 1220 7073 1220 7074 1220 7075 1220 NOTE 1 Attentuators will result in an additional external resistance therefore the fan will be unable to deliver the same airflow resulting in a small reduction in performance.
Marley Fluid Cooler Fluid Cooler Coil When the ambient temperature falls below 0°C, heat loss from the coil can be substantial even without recirculating water flowing over the coil. The process fluid, without an applied heat load, may be prone to freezing.
Marley Fluid Cooler The MC Fluid Cooler can be a very effective air washer. Atmospheric dust able to pass through the relatively small louver openings will enter the recirculating water system. Increased concentrations can intensify systems maintenance by clogging screens and strainers—and smaller particulates can coat system heat transfer surfaces.
Marley Fluid Cooler Specifications Base: Furnish and install a forced-draft, coun- terflow-type, factory assembled, film fill, industrial duty, galvanized steel, closed circuit fluid cooler. Unit shall consist of _____ cell(s), as shown on plans. The limiting overall dimensions of the fluid cooler shall be _____ wide, _____ long, and _____ high.
Marley Fluid Cooler Specifications the test and will make such corrections as are appropriate and agreeable to the owner to compensate for the perfor- mance deficiency. Coil: 4.1 Coil(s) shall consist of fully welded box headers with serpentine coils and hot-dip galvanized after fabrication. Coils shall be tested to 2757 kPa air pressure while immersed in water.
Marley Fluid Cooler Specifications take the above water quality and load carrying capabilities into account in the selection of their materials of manufac- ture. Mechanical Equipment: 7.1 Fan(s) shall be forward curved cen- trifugal-type, which are statically and dynamically balanced. The fan impeller is manufactured from galvanized steel, blades are riveted to the center plate and inlet rings and have stay rods to ensure maximum concentricity and...
Marley Fluid Cooler Specifications Drift Eliminators: 8.1 Drift eliminators shall be PVC, triple pass and shall limit drift losses to no more than 0.005% of the design water flow rate. Hot Water Distribution System: A pressured spray system shall distrib- ute water evenly over the fill. Header box shall be steel and branch arms shall be PVC with polypropylene spray nozzles attached to the branch arms by an integral screw connection for ease...
Marley Fluid Cooler Specifications Convenience and Safety Options Top Access Platform: 11.2 Add the following paragraph in the Access section: There shall be an access platform at the top of the fluid cooler to allow access to the drift eliminators and distribution system. The platform shall be free-standing galvanized steel bar grating, sup- ported by galvanized steel framework.
Marley Fluid Cooler Specifications Access Door Platform: 11.4 Add the following paragraph in the Access section: There shall be an access platform at the base of the fluid cooler extending across the width of the casing. The platform shall be gal- vanized steel bar grating, supported by galvanized steel framework attached to the fluid cooler.
Marley Fluid Cooler Specifications temperature at the coil and the other for set point. Process temperature input shall be obtained using a thermal sens- ing device on the process coil and wired back to the solid state temperature controller in the control panel. Staging of multiple motors and speeds will be accomplished with an integral PLC.
Marley Specifications: Options Fluid Cooler Specifications Specification Value in the off position for safety. The VFD system shall receive a speed reference signal from the Building Management System monitoring the tower fluid tem- perature. As an option to receiving the speed reference signal from a building management system, the drive must have the capability to receive a 4-20 ma temperature signal from an RTD trans- mitter. The VFD shall have an internal PI...
Page 25
Marley Specifications: Options Fluid Cooler Specifications Specification Value teeth or drive shafts. The VFD shall catch a fan spinning in the reverse direction without tripping. The panel shall include a main disconnect with short circuit pro- tection and external operating handle, lockable in the off position for safety. The system shall include a solid state, PI temperature controller to adjust fre- quency output of the drive in response...
Marley Fluid Cooler Specifications Miscellaneous Options Sound Control Add the following paragraph under Base: The fluid cooler shall be quiet operation, and shall produce an overall level of sound not higher than _______ dB(A) measured at the critical location indicated on the plans. Specifications: Options Specification Value Sound produced by a standard MC Fluid Cooler operating in an ■...
Marley Fluid Cooler Specifications Discharge Hood: Add the following paragraph to the Mechanical Equipment Section: There shall be a galva- nized steel tapered duct on the discharge side of the fluid cooler. Drift eliminators shall be reposi- tioned into the lower section of the duct.