Carrier AquaEdge 19XRV Installation Instructions Manual page 44

Single-stage semi-hermetic centrifugal liquid chillers with pic iii controls and hfc-134a 50/60 hz
Table of Contents

Advertisement

FRAME
PRESSURE
SIZE
PSIG (KPA)
150/300
2
(1034/2068)
150/300
3
(1034/2068)
150/300
4
(1034/2068)
150/300
5
(1034/2068)
150/300
6
(1034/2068)
150
(1034)
7
300
(2068)
150
(1034)
8
300
(2068)
Table 9 — 19XRV Waterbox Nozzle Sizes
NOMINAL PIPE SIZE (IN.)
PASS
COOLER
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
8
3
6
1
10
2
10
3
8
1
14
2
12
3
10
1
14
2
12
3
10
1
14
2
14
3
12
1
14
2
14
3
12
44
ACTUAL PIPE ID (IN.)
CONDENSER
COOLER
10
10.020
8
7.981
6
6.065
10
10.020
8
7.981
6
6.065
10
10.020
8
7.981
6
6.065
10
10.020
10
7.981
8
6.065
10
10.020
10
10.020
8
7.981
14
13.250
12
12.000
12
10.020
14
12.500
12
11.376
12
9.750
14
13.250
14
13.250
12
12.000
14
12.500
14
12.500
12
11.376
CONDENSER
10.020
7.981
6.065
10.020
7.981
6.065
10.020
7.981
6.065
10.020
10.020
7.981
10.020
10.020
7.981
13.250
12.000
12.000
12.500
11.376
11.750
13.250
13.250
12.000
12.500
12.500
11.376

Advertisement

Table of Contents
loading

Table of Contents