START UP

Caution!
b
Risk of material damage
Comply with electrical cable
routing
Avoid any contact with hot parts
(heating coil).
Keep a distance of 10mm between
connecting cables and metallic
elements that are a heat source.
To guarantee the minimum
tension at the cables, the screwed
connections on the power supply
cable and the relay control cable
must be tightened sufficiently.
Strain relief: 100N (10kg)
2
1
1
Power cable (*)
2
Relay command cable
(*)
i
Notes
The temperature probe must be assembled
using thermal paste for good heat transfer.
5
Start up
► For fi lling, refer to the installation instructions of the heat
pump.
► Check the electrical and water installation.
► Check all connections for leaks..
► Fill the heating installation.
► Purge your heating system.
► Replace the power.
12
3
3
Temperature probe cable
(Sensor included no
mounting)
(*) Not included
Danger!
e
Risk of death from electric shock!
Before carrying out the following
work, ensure that the product has
been disconnected from the
power supply.
5.1

Purging the appliance

1
1
Air vent
► Open the air vent (1), when fi lling the heating circuit with
water.
Caution!
b
Risk of damage in case of bad
purge!
If air purging is not done properly,
this may cause damage to the
electrical heating element.
Make sure the heating circuit is
properly purged air.
Caution!
b
Risk of material damage
When purging the air from the
resistance, avoid all risk of water
projection onto the electrical
components.
0020152779_05 - 10/14 - Vaillant