Vaillant VWZ MEH 60 Installation Instructions And Instructions For Use page 10

Hide thumbs Also See for VWZ MEH 60:
Table of Contents

Advertisement

MOUNTING AND INSTALLATION
3-phase supply cable
Heating element relay cable
3
2
1
1
Electrical casing
2
230 V electrical
connection label
Caution!
b
Risk of damage from too great
voltage.
At mains voltages higher than 253 V,
electronic components may be
destroyed.
Make sure that the rated voltage
of the mains is 230 V.
Caution!
b
Risk of damage from too great
voltage.
At mains voltages higher than 400 V,
electronic components may be
destroyed.
Make sure that the rated voltage
of the mains is 400 V.
► Connect alimentation cables of product on the electrical
panel of installation.
10
400 V (5 x 1,5 mm²)
230 V (3 x 0,75 mm²)
3
400 V electrical
connection label
4.4.1.1
Method of collection of electrical cables
B
4.4.1.2
230 V connection - Cable routing 6 kW
Caution!
b
Comply with the instructions on
the label affixed inside the electri-
cal casing.
N1 L3
N L
L2
L
1
2
3G4
1
Protection mini. 30A
4.4.1.3
230 V connection - Cable routing 4 kW
Caution!
b
Comply with the instructions on
the label affixed inside the
electrical casing.
Caution!
b
For 230V connection, you must
remove the shunts between L2
and L3.
A
C
L1
02 01
N 1 2
L
3
1
0020152779_05 - 10/14 - Vaillant