Before installation

The drive must be installed in an upright position with the cooling section facing a
wall. Check the installation site according to the requirements below. Refer to
chapter

Requirements for the installation site

See chapter

Wall

The wall should be as close to vertical as possible, of non-flammable material and
strong enough to carry the weight of the unit. Check that there is nothing on the wall
to inhibit the installation.

Floor

The floor/material below the installation should be non-flammable.

Free space around the unit

Required free space around the drive to enable cooling air flow, service and
maintenance is shown below in millimetres and [inches].
50 [2.0]
IP 21 (UL 1)
Dimensional drawings
Technical data
200 [7.9]
50 [2.0]
200 [7.9]
for frame details.
for the allowed operation conditions of the drive.
Cooling air flow
Mechanical installation