15. ELECTRICAL CONNECTIONS

The electrical installation must be performed by a fully qualified electrician, and in accordance with local electrical
standards and the wiring diagram corresponding to the unit model.
Any modification performed without our prior authorisation may result in the unit's warranty being declared null
and void.
The power supply cable section must be sufficient to provide the appropriate voltage to the unit's power supply
terminals, both at start-up and under full load operating conditions.
The power supply cable shall be selected in accordance with the following criteria:
1. power supply cable length.
2. maximum unit starting current draw – the cables shall supply the appropriate voltage to the unit
terminals for starting.
3. power supply cables' installation mode.
4. Cables' capacity to transport the total system current draw.
Short circuit protection shall be provided. This protection shall comprise fuses or circuit breakers with high breaking
capacity, mounted on the distribution board.
If the local control includes an remote ambient temperature sensor and/or a set temperature adjustment module,
these shall not pass through the same conduits as the power supply cables as the voltages induced may create
reliability faults in the unit's operation.
On-site wiring must be performed in accordance with the wiring diagram present in the appliance's
electrical connection box.
Mains power supply cables to the appliance must have copper conducting cores and be sized in
compliance with currently applicable IEC standards.
The appliance must be grounded via a terminal block located inside the electrical connection box.
The power supply must not fluctuate by more than 10 %. Imbalance between phases must not
exceed 3%.
A circuit breaker or fuse holder ( not supplied ) must be installed on the main power supply of the unit in accordance
with the circuit diagram; for the raitings, refer to the electrical specifications.
Before carrying out any work on the equipment,
make sure that the electrical power supply is
disconnected and that there is no possibility
of the unit being started inadvertently.
Non-compliance with the above instructions
can lead to injury or death by electrocution.
WARNING!