13.2.1. AWAU-YvD005-H11
A: Gas line
E: Flare union
B: Liquid line
F: Adapter supplied with the unit
C: pipe insulation
13.2.2. AWAU-YvD008-H11 - AWAU-YvD012-H11 - AWAU-YvD014-H11
A: Gas line
C: pipe insulation
E: Flare union
B: Liquid line

13.3. ASSEMBLY

Connect the connecting pipes to the units by FLARE NUTS
²
To obtain the right tightening, cover the surface with cooling oil.
²
The use of a counter wrench is required to tighten the valves.
²
The values of the tightening torque are shown in the table below.
1/2"
E
F
1/4"
B
A
5/8"
E
3/8"
B
25
A
C
E
C
E
Ø
CONNECTION
1/4"
3/8"
1/2"
5/8"
TIGHTENING
TORqUE
14-18 Nm
33-42 Nm
50-62 Nm
63-77 Nm