Test Operation - Toshiba RAS-B10SKVP-E Installation Manual

Hide thumbs Also See for RAS-B10SKVP-E:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
01_Installation_EN.fm Page 16 Tuesday, December 26, 2006 4:36 PM

6 TEST OPERATION

Gas Leak Test
• Check the flare nut connections for gas leaks with a
gas leak detector and/or soapy water.
Test Operation
To test the system, press and hold RESET button for 10 sec.
(There will be one short beep.)
Auto Restart Setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power
failure.
INFORMATION
INFORMATION
The product was shipped with Auto Restart function in the OFF position. Turn it ON as required.
How to set the Auto Restart
• Press and hold the RESET button for about 3 seconds. After 3 seconds, three short electric beeps will be heard to inform you that
the Auto Restart has been selected.
• To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner's Manual.
If the air conditioner operates incorrectly
• If two indoor units are installed in the same room or adjoining rooms, when the user tries to operate only one unit, both units may
receive the same remote controller signal and operate. This can be prevented by changing one of the indoor units and remote
controllers to setting "B" (the default setting for both units is "A").
• If the indoor unit and remote controller settings are different, the remote controller signal is not accepted.
1.
Setting the remote controller
a Slide open the remote controller cover and remove the batteries.
b Cut the jumper wire inside the battery compartment using nippers.
• The jumper wire should not remain in contact after being cut. Also,
be careful not to let plastic scraps, jumper wire cuttings or other
debris enter the inside of the remote controller.
c Insert the batteries. "B" appears in the remote controller display.
2.
Setting the unit
Press the RESET button to start automatic operation.
3.
Press the
button of the remote controller that was set in step 1 to
stop the air conditioner. (This operation will change the setting to "B".)
4.
Check that the remote controller operates the indoor unit.
EN
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
16
www.heronhill.co.uk
Valve cover
Check
places for
indoor unit
Electric parts cover
Check places for outdoor unit
RESET button
Jumper wire
When switching between
settings "A" and "B", always
switch the indoor unit board
and the remote controller as a
pair. (Otherwise, the indoor
unit will not accept the remote
controller's signals.)
RESET button
Fax: 01823 665807
Cutting direction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents