CAUTION
• Drain piping connections
Do not connect the drain piping directly to sewage pipes that smell of ammonia. The ammonia in the sew-
age might enter the indoor unit through the drain pipes and corrode the heat exchanger.
• Keep in mind that it will become the cause of getting drain pipe blocked if water collects on drain pipe.

8. ELECTRIC WIRING WORK

8-1
GENERAL INSTRUCTIONS
• All field supplied parts and materials and electric works must conform to local codes.
• Use copper wire only.
• For electric wiring work, refer to also
• For remote controller wiring details, refer to the installation manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each indoor unit as unit A, unit B..., and be sure the
terminal board wiring to the outdoor unit and BS unit are properly matched. If wiring and piping between
the outdoor unit and an indoor unit are mismatched, the system may cause a malfunction.
• A circuit breaker capable of shutting down power supply to the entire system must be installed.
• Refer to the installation manual attached to the outdoor unit for the size of power supply wiring connected
to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.
• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas and water pipes, lightning rods, or telephone ground wires.
:
• Gas pipes
might cause explosions or fire if gas leaks.
• Water pipes : no grounding effect if hard vinyl piping is used.
• Telephone ground wires or lightning rods : might cause abnormally high electric potential in the ground
during lighting storms.
8-2
ELECTRICAL CHARACTERISTICS
Model
Hz
FXZQ20MVE
FXZQ25MVE
FXZQ32MVE
50
FXZQ40MVE
FXZQ50MVE
FXZQ20MVE
FXZQ25MVE
FXZQ32MVE
60
FXZQ40MVE
FXZQ50MVE
MCA: Min. Circuit Amps (A)
kW:
Fan Motor Rated Output (kW)
English
"
Wiring diagram label
Units
Volts
Voltage range
Max. 264
220-240
Min. 198
Max. 242
220
Min. 198
MFA: Max. Fuse Amps (A)
FLA: Full Load Amps (A)
"
attached to the control box lid.
Power supply
MCA
MFA
0.8
15
0.8
15
0.8
15
0.8
15
0.9
15
0.8
15
0.8
15
0.8
15
0.8
15
0.9
15
Fan motor
kW
FLA
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.7
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.7