ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
NOTES: A.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
B.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
C.
Circuit breakers for 3-phase (3Ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
IMPORTANT: Figures shown are for non-reversing models ONLY.
IMPORTANT: The wire size must be properly sized to handle the related current.
NOTE: Manufacturer reserves the right to make changes in specifications at any time without notice or
obligation.
CG20
PHASE
SERVICE
120
208
240
208
240
380
400
416
18
APPROX.
WIRE
AMP DRAW
60 Hz 50 Hz
2
10.9
---
2/3
6.2
---
3
5.8
3
35
---
3
39.3
39.5
4
---
16.3
4
---
16.5
4
---
17
CIRCUIT
BREAKER
15
15
6
15
40
40
20
20
20
040403