Xp180/240 Unit Clearances; Xp180/240 Unit Dimensions Rain Hood; Xp180/240 Roof Curb - York XP SERIES W/SIMPLICITY Installation Manual

15/20 ton 60 hertz
Table of Contents

Advertisement

5168273-YIM-A-1115
Power Exhaust
Rain Hood
Supply Air
(on Return
Compartment
Air Compartment)
Rear View
Figure 10: XP180/240 Unit Dimensions Rain Hood
Table 4: XP180/240 Unit Clearances
Direction
1
Top
Front
Rear
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
3. If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of the
evaporator coil, or in the outdoor air compartment, prior to final installation.
Note: Units and ductwork are approved for zero clearance to combustible material when equipped with electric
heaters.
Figure 11: XP180/240 Roof Curb
12
Economizer Motorized
Damper Rain Hood
(on Outdoor
Air Compartment)
Unit with Rain Hoods
Distance (in.)
72 With 36 Maximum Horizontal Overhang
(For Condenser Air Discharge)
36
24 (W/O Economizer)
49 (W/Economizer)
25-1/4"
Economizer/Motorized Damper
and Power Exhaust Rain Hood
36-5/8"
16-1/8"
5"
28-3/16"
Detail "Y"
Direction
Right
2
Bottom
Left
Fixed
Outdoor Air
Intake Hood
(Located on
Return Air
1" Condensate
Compartment)
Drain (Must be
Trapped)
92"
LH View
Distance (in.)
36
0
24 (W/O Economizer)
36 (W/Economizer)