Technical Data - ABB RET670 Product Manual

Hide thumbs Also See for RET670:

Advertisement

Transformer protection RET670
Pre-configured
Product version: 1.1

7. Technical data

General
Definitions
Reference
The specified value of an influencing factor to which are referred the
value
characteristics of the equipment
Nominal
The range of values of an influencing quantity (factor) within which, under
range
specified conditions, the equipment meets the specified requirements
Operative
The range of values of a given energizing quantity for which the equipment,
range
under specified conditions, is able to perform its intended functions
according to the specified requirements
Energizing quantities, rated values
and limits
Analog inputs
Table 4. TRM - Energizing quantities, rated values and limits
Quantity
Current
Operative range
Permissive overload
Burden
Ac voltage
Operative range
Permissive overload
Burden
Frequency
*)
max. 350 A for 1 s when COMBITEST test switch is included.
42
Rated value
I
= 1 or 5 A
r
(0-100) x I
r
4 × I
cont.
r
*)
100 × I
for 1 s
r
< 150 mVA at I
= 5 A
r
< 20 mVA at I
= 1 A
r
U
= 110 V
r
(0–340) V
420 V cont.
450 V 10 s
< 20 mVA at 110 V
f
= 50/60 Hz
r
1MRK 504 091-BEN B
Issued: June 2010
Nominal range
(0.2-40) × I
r
0.5–288 V
± 5%
ABB