Table 59. Configurable logic blocks
Logic block
Quantity with cycle time
fast
LogicAND
60
LogicOR
60
LogicXOR
10
LogicInverter
30
LogicSRMemory
10
LogicGate
10
LogicTimer
10
LogicPulseTimer
10
LogicTimerSet
10
LogicLoopDelay
10
Monitoring
Table 60. Measurements CVMMXN
Function
Frequency
Voltage
Connected current
Active power, P
Reactive power, Q
Apparent power, S
Power factor, cos (φ)
Range or value
medium
normal
-
60
160
60
160
-
10
20
-
30
80
-
10
20
-
10
20
-
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
10
20
(0.000–90000.000) s
Range or value
(0.95-1.05) × f
r
(0.1-1.5) ×U
r
(0.2-4.0) × I
r
0.1 x U
< U < 1.5 x U
r
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
r
0.2 x I
< I < 4.0 x I
r
r
0.1 x U
< U < 1.5 x U
r
r
0.2 x I
< I < 4.0 x I
r
r
1MRK 504 091-BEN B
Issued: June 2010
Accuracy
-
-
-
-
-
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
Accuracy
± 2.0 mHz
± 0.5% of U
at U£U
r
r
± 0.5% of U at U > U
r
± 0.5% of I
at I £ I
r
r
± 0.5% of I at I > I
r
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
r
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
r
± 1.0% of S
at S ≤ S
r
r
± 1.0% of S at S > S
r
± 0.02