CLEARANCES TO COMBUSTIBLE MATERIALS / FLOOR PROTECTION
• The location should also be free of electrical, plumbing or other heating/air conditioning
ducting.
• Due to high temperatures, this appliance should be located out of traffi c and away from
furniture, draperies and not in windy or drafty areas.
• This appliance can be installed in most residential room confi gurations, parallel to a rear
or adjacent wall, or in an alcove that allows for the minimum clearances to combustible
surfaces. Your local building inspector should review your plans prior to installation.
• When installing this appliance, provide adequate clearances for the purposes of servicing
and proper operation.
• As determined through the safety certifi cation of this unit, a minimum clearance to
combustible materials must be maintained around specifi c areas of the gas appliance. (See
Table 5 and Figure 2)
A (minimum)
B (minimum)
C (minimum)
D (minimum)
E (minimum)
F (minimum)
G (minimum)
H (minimum)
I (minimum)
J (MAXIMUM)
* Dimensions with a single asterix are reference dimensions only.
** If the optional warming shelves are installed, a greater alcove width is required as follows:
CI1500DVF - 44" (1118 mm) min.
CI2500DVF - 52-1/2" (1334 mm) min.
***This includes any projections such as shelves, windowsills, mantels, etc. above the appliance.
Note: Recommended clearance zone from the front of the appliance to combustibles is 36 inches
(914 mm) minimum.
Table 5
Floor Protection
When installed directly on carpeting, tile (see Note below) or other combustible material other
than wood fl ooring, the appliance shall be installed on a metal or wood panel extending the
full width and depth of the stove body.
Note: Ceramic tile is non-combustible and does not require a wood or metal panel under the
appliance.
Vent Clearances - All Models
For Horizontal Sections:
Top - 3" (76.2 mm) min.
Sides - 1" (25.4 mm) min.
Bottom - 1" (25.4 mm) min.
For Vertical Sections:
Sides - 1" (25.4 mm) min.
Clearances
CI1500DVF
*10" (254 mm)
*14-1/4" (362 mm)
*15-7/8" (403 mm)
4"(102 mm)
2" (51 mm)
4" (102 mm)
0" (0 mm)
***62" (1575 mm)
**28-1/2" (724 mm)
**34-1/2" (876 mm)
48" (1219 mm)
At Wall Firestops:
Top - 3" (76.2 mm) min.
Sides - 1" (25.4 mm) min.
Bottom - 1/2" (12.7 mm) min.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
CI2500DVF
*10" (254 mm)
*17-1/4" (438 mm)
*19" (483 mm)
4"(102 mm)
2" (51 mm)
4" (102 mm)
0" (0 mm)
***62" (1575 mm)
48" (1219 mm)
Clearance To Combustibles
and Alcove Dimensions
Side View / Rear Wall or Alcove Clearances
H
L
E
N
N
O
X
G
J
Top View / Rear Wall or Alcove Clearances
D
*B
E
I
Top View / Corner Clearances
F
Figure 2
*A
D
E
*C
F
5