4.9.17 - GENCONF menu
NAME
FORMAT
ramp_sel
Yes/No
off_on_d
1 to 15
nh_start
00:00 to 24:00
nh_end
00:00 to 24:00
bas_menu
0 to 3
synoptic
Yes/No
4.9.18 - PUMPCONF menu
NAME
FORMAT
pump_seq
Yes/No
pump_per
Yes/No
pump_sby
Yes/No
pump_loc
Yes/No
4.9.19 - HCCONFIG menu
NAME
FORMAT
hr_sel
0 to 3
heat_th
-20 to 0
boil_th
-30 to 15
ehs_th
-5 to 21
ehs_back
Yes/No
ehs_pull
0 to 60
ehs_defr
Yes/No
4.9.20 - RESETCFG menu
NAME
FORMAT
oathr_non
-10 to 51.7
oathr_fu
-10 to 51.7
dt_hr_non
-17.8 to -3.9
dt_hr_fu
-17.8 to -3.9
v_hr_non
-17.8 to -6.7
v_hr_fu
-17.8 to -6.7
hr_deg
-34.4 to 1.1
4.9.21 - USERCONF menu
NAME
FORMAT
language
0 to 5
use_pass
1 to 9999
4.9.22 - DATETIME menu
NAME
FORMAT
hour
0 to 24
minutes
0 to 59
dow
1 to 7
tom_hol
No/Yes
tod_hol
No/Yes
dlig_off
No/Yes
dlig_on
No/Yes
d_of_m
1 to 31
month
1 to 12
year
0 to 99
4.9.23 - CTRL_ID menu
NAME
FORMAT
elemt_nb
1 to 239
bus_nb
0 to 239
baudrate
9600 to 38400
12
DEFAULT
UNIT
No
-
1
min
00:00
-
00:00
-
0
-
No
-
DEFAULT
UNIT
No
-
No
-
No
-
Yes
-
DEFAULT
UNIT
0
-
-15
°C
-25
°C
5
°C
No
-
0
minutes
No
-
DEFAULT
UNIT
-10
°C
-10
°C
-17.8
^C
-17.8
^C
-17.8
^C
-17.8
^C
-17.8
^C
DEFAULT
UNIT
0
-
11
-
DEFAULT
UNIT
hours
minutes
-
No
-
No
-
-
-
-
-
-
DEFAULT
UNIT
1
-
0
-
9600
-
61 AF Pro-Dialog+
CSA-SR-20H430NN
-
DESCRIPTION
Ramp loading sequence
Start-up delay
Night mode start hour
Night mode stop hour
Basic menu configuration
0 = total access
1 = access to the alarm menu by password
2 = access to the setpoint menu by password
3 = combination of 1 and 2
Synoptic diagram display
DESCRIPTION
Heat exchanger pump availability
Pump seizure protection
Pump shutdown when the unit is in standby
Flow rate verification when the pump has shut down
DESCRIPTION
Heating reset selection
1 = outside temp., 0 = none, 2 = delta T
Outside temperature threshold heating mode
Outside temperature threshold for the boiler
Outside temperature threshold for electric heater stages
One backup electric heater stage
Delay before start-up of the first electric heater stage
Quick electric heat stages for defrost
DESCRIPTION
Outside temperature for no reset
Outside temperature for maximum reset
Delta T for no reset
Delta T for maximum reset
Current value for no reset
Current value for maximum reset
Heating mode reset value
DESCRIPTION
Language selection
English = 0, Spanish = 1, French = 2, German = 3, Italian = 4,
Translation = 5
User password
DESCRIPTION
Hour
Minutes
Day of the week
Holiday tomorrow?
Holiday today?
Winter time change-over active?
Summer time change-over active?
Day of the month
Month
Year
DESCRIPTION
Element number
Bus number
Communication speed
Description
Software version
Serial number

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents