4.9.5 - INPUTS menu
NAME
FORMAT
ONOFF_SW
Open/Close
SETP_SW
Open/Close
LIM_SW1
Open/Close
FLOW_SW
Open/Close
leak_v
nn.n
Lock_sw2
Open/Close
4.9.6 - OUTPUTS menu
NAME
FORMAT
CP_A1
On/Off
CP_A2
On/Off
FAN_A1
0 to 2
FAN_A2
0 to 2
EXV_A
nnn
EXV_ECO
nnn
EV_VALV1
On/Off
EV_VALV2
On/Off
RV_A
On/Off
EXC_HEAT
On/Off
BOILER
On/Off
EHS_STEP
n
PUMP_1
On/Off
ALARM
On/Off
RUNNING
On/Off
4.9.7 - RUNTIME menu
NAME
FORMAT
HR_MACH
nnnnn
st_mach
nnnnn
HR_CP_A1
nnnnn
st_cp_a1
nnnnn
HR_CP_A2
nnnnn
st_cp_a2
nnnnn
hr_fana1l
nnnnn
hr_fana1h
nnnnn
hr_fana2l
nnnnn
hr_fana2h
nnnnn
hr_pump
nnnnn
4.9.8 - MODES menu
NAME
FORMAT
m_limit
Yes/No
m_ramp
Yes/No
m_cooler
Yes/No
m_SM
Yes/No
m_leadla
Yes/No
m_night
Yes/No
m_heater
Yes/No
m_boiler
Yes/No
m_defr_a
Yes/No
m_sst_a
Yes/No
m_dgt_a
Yes/No
m_hp_a
Yes/No
m_sh_a
Yes/No
4.9.9 - ALARMS menu
NAME
ALARMRST
CUR_ALRM
ALMHIST1
4.9.10 - CONFIG menu
NAME
GEN_CONF
PUMPCONF
HC_CONFIG
RESETCFG
USERCONFIG
SCHEDULE
HOLIDAY
BRODCAST
DATETIME
DISPLAY
CTRL_ID
10
UNIT
DESCRIPTION
-
Remote start/stop contact
-
Remote setpoint contact
-
Remote capacity limitation contact
-
Water flow rate/customer safety loop contact
Volt
Leak detector value
-
Customer safety loop contact
UNIT
DESCRIPTION
-
Compressor output A1
-
Compressor output A2
-
Fan speed A1
-
Fan speed A2
%
Main EXV position
%
EXV Eco position
-
Shut-off valve compressor A1/EXV Eco
-
Shut-off valve compressor A2/EXV Eco
-
Four-way valves
-
Heat exchanger heater
-
Boiler command
-
Electric heater stage
-
Output pump 1
-
Alarm relay
-
Unit on relay
UNIT
DESCRIPTION
hours
Number of unit operating hours
-
Number of unit start-ups
hours
Number of operating hours compressor A1
-
Number of start-ups compressor A1
hours
Number of operating hours compressor A2
-
Number of start-ups compressor A2
hours
Number of low-speed operating hours fan A1
hours
Number of high-speed operating hours fan A1
hours
Number of low-speed operating hours fan A2
hours
Number of high-speed operating hours fan A2
hours
Number of pump operating hours
UNIT
DESCRIPTION
-
Capacity limitation active
-
Ramp loading active
-
Heat exchanger heater active
-
Aquasmart active
-
Master/slave active
-
Low-noise level night mode active
-
Electric heater stages active
-
Boiler active
-
Defrost active
-
Low suction temperature
-
High discharge gas temperature
-
High pressure
-
High pressure
DESCRIPTION
Alarm reset
Current alarms
Alarm history
DESCRIPTION
General configuration menu
Pump configuration menu
Heating mode configuration menu
Reset configuration menu
User configuration menu
Time schedule
Holiday calendar
Summer time/winter time control
Time adjustment
Parameter display
Control identification

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents