Installation; Typical Roof Mounting Installation; Typical Motor Wiring Diagram - Greenheck ERCH-20 Installation, Operation And Maintenance Manual

Energy recovery ventilator with heating and cooling
Table of Contents

Advertisement

Installation

Typical Roof Mounting Installation

1. On the roof surface, cut an appropriate sized hole
and follow manufacturer's instructions on curb
installation. Caulk and flash the curb to ensure a
water tight seal.
Roof Curb Installation
2. If unit is equipped with a backdraft damper, it
should be installed now.
3. Remove motor cover. Access to the motor
compartment is accomplished by removing the
screws as shown in Figure 3, page 2.
4. On GB Belt Drive fans, use the lifting lugs on the
drive frame or bearing plate to lift and place the
unit on top of roof curb. Refer to Figure 2, page 2.
5. On G Direct Drive fans, lift and place the unit on
top of roof curb using hooks under the lip of the
shroud. Refer to Figure 1, page 2.
6. Secure fan to curb using a minimum of eight lag
screws, metal screws or the suitable fasteners.
Shims may be required depending upon curb
installation and roofing material.
Note: Severe duty applications may require
additional fasteners. See page 6.
7. Verify power line wiring is de-energized before
connecting fan motor to power source.
8. Connect power supply wiring to the motor as
indicated on the motor nameplate or terminal box
cover. Check the power source for compatibility
with the requirements of your equipment.
9. Check fan wheel for free rotation, recenter if
necessary.
4
Downblast Centrifugal Roof Exhaust
10. Check all fasteners for tightness.
11. Mount and wire safety disconnect switch under
motor cover. Wire control switches at ground
level, refer to Figure 4.
12. Replace motor cover.
Typical Wiring Diagram
MOTOR
SUPPLY VOLTAGE
115/208-230/60/1
J-BOX
L1
L2
Figure 4
Vari-Green Wiring
For Vari-Green wiring, refer to the Vari-Green
Motor and Controls Installation, Operation and
Maintenance Manual for complete wiring and
operation instructions.
MOTOR
SUPPLY VOLTAGE
208-230/460/60/3
J-BOX
L1
L2
L3
®