Rail Mounting/Layout; Duct Connections - Greenheck ERCH-20 Installation, Operation And Maintenance Manual

Energy recovery ventilator with heating and cooling
Table of Contents

Advertisement

Rail Mounting / Layout
1. Rails designed to handle the weight of the unit
should be positioned as shown on the diagram (rails
by others).
2. Make sure that rail positioning does not interfere with
the supply air discharge opening or the exhaust air
intake opening on the unit. Avoid area dimensioned
"B" below.
3. Rails should run the width of the unit and extend
beyond the unit a minimum of 12 inches on each
side.
4. Set unit on rails.
B
Rail Mounting
Unit Size
ERCH-20
ERCH-45
ERCH-55
ERCH-90
All dimensions are in inches.
Ductwork Connections
Examples of poor and good fan-to-duct connections
are shown. Airflow out of the fan should
be directed straight or curve the
same direction as the
fan wheel rotates. Poor
duct installation will result
in low airflow and other
system effects.
Length of Straight Duct
GOOD
Inlet/Outlet Descriptions
Code Description
OIE
Outdoor Air Intake End
OIT
Outdoor Air Intake Top
RIE
Return Air Intake End
RIS
Return Air Intake Side
RIB
Return Air Intake Bottom
RIT
Return Air Intake Top
SDE
Supply Discharge End
®
A
A
B
5.0
41.0
7.0
41.9
5.5
53.0
6.0
59.0
POOR
Code Description
SDT
Supply Discharge Top
SDT/IG Supply Discharge Top w/IG
SDS
Supply Discharge Side
SDB
Supply Discharge Bottom
EDE
Exhaust Discharge End
EDT
Exhaust Discharge Top
EDS
Exhaust Out Side
ERCH-20
Intake Duct Size Discharge
OIE
22 x 26
SDE
OIT
24 x 20
SDS
RIE
16 x 32
SDT
RIS
18 x 30
SDT/IG
RIB
16 x 32
SDB
RIT
16 x 32
EDE
EDT
EDS
ERCH-45
Intake Duct Size Discharge
OIE
28 x 36
SDE
OIT
34 x 24
SDS
RIE
24 x 40
SDT
RIS
26 x 32
SDT/IG
RIB
20 x 48
SDB
RIT
28 x 30
EDE
EDT
EDS
ERCH-55
Intake Duct Size Discharge 12-12 Blower 15-15 Blower
OIE
32 x 52
SDE
OIT
40 x 28
SDS
RIE
30 x 40
SDT
RIS
30 x 38
SDT/IG
RIB
20 x 54
SDB
RIT
30 x 40
EDE
EDT
EDS
ERCH-90
Intake Duct Size Discharge 15-15 Blower 18-18 Blower
OIE
34 x 64
SDE
OIT
34 x 50
SDS
RIE
32 x 60
SDT
RIS
40 x 40
SDT/IG
RIB
22 x 74
SDB
RIT
40 x 40
EDE
EDT
EDS
All dimensions shown in inches.
• Recommended duct sizes are based on velocities across the cfm
range of each model at approximately 800 feet per minute (FPM) at
minimum airflow and up to 1600 fpm at maximum airflow.
• Recommended duct sizes are only intended to be a guide and
may not satisfy the requirements of the project. Refer to plans for
appropriate job specific duct size and/or velocity limitations.
Energy Recovery Ventilator with Heating and Cooling
General Description - NOT model specific
Recommended Duct Size
9-9 Blower
10-6 Blower
16 x 16
16 x 16
16 x 16
16 x 16
16 x 16
16 x 16
28 x 24
28 x 24
12 x 14
12 x 14
16 x 16
16 x 16
16 x 16
16 x 16
16 x 16
16 x 16
Recommended Duct Size
12-8 Blower
9-9 Blower
12-12 Blower
20 x 20
16 x 16
20 x 20
16 x 16
20 x 20
16 x 16
28 x 28
28 x 28
16 x 18
16 x 18
20 x 20
16 x 16
20 x 20
16 x 16
20 x 20
16 x 16
Recommended Duct Size
20 x 20
28 x 28
20 x 20
28 x 28
20 x 20
28 x 28
38 x 30
38 x 30
16 x 18
18 x 20
20 x 20
28 x 28
20 x 20
28 x 28
20 x 20
28 x 28
Recommended Duct Size
28 x 28
32 x 32
28 x 28
32 x 32
28 x 28
32 x 32
34 x 34
34 x 33
18 x 20
20 x 24
28 x 28
32 x 32
28 x 28
32 x 32
28 x 28
32 x 32
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erch-55Erch-90Erch-45

Table of Contents