Carrier 38GJ Owner's Manual & Installation Instructions page 2

Multi-zone ductless split system sizes 30 to 42
Table of Contents

Advertisement

SAFETY
CONSIDERATIONS
Installing,
starting
up, and servicing
air-conditioning
equipment
can be hazardous
due to system
pressures,
electrical
components,
and equipment
location
(roofs,
elevated
structures,
etc.).
Only
trained,
qualified
installers
and service
mechanics
should
install, start-up,
and service this equipment.
Untrained
personnel
can perform
basic maintenance
flmctions
such
as cleaning
coils. All other
operations
should
be performed
by
trained
service personnel.
When
working
on the
equipment,
observe
precautions
in the
literature
and
on
tags,
stickers,
and
labels
attached
to
the
equipment.
Follow
all safety codes. Wear safety glasses and work gloves.
Keep
quenching
cloth and fire extinguisher
nearby
when
brazing.
Use
care in handling,
rigging,
and setting bulky
equipment.
Read
these
instructions
thoroughly
and follow
all warnings
or
cautions
included
in literature
and
attached to the unit.
Consult
local
building
codes
and National
Electrical
Code
(NEC)
for
special
requirements.
Recognize
safety
information.
This
is the
safety-alert
symbol/}k
When you see this symbol
on the unit and
in instructions
or manuals,
be alert to the potential
for personal
injury.Understand
these signal words:
DANGER,
WARNING,
and
CAUTION.
These words
are used with the safety-alert
symbol.
DANGER
identifies
the most serious
hazards
which
will result in
severe
personal
injury
or death.
WARNING
signifies
hazards
which could
result in personal
injury or death.
CAUTION
is used
to identify
unsafe
practices
which
may
result
in nfinor
personal
injury or product
and property
damage.
NOTE is used to highlight
suggestions
which will result in enhanced
installation,
reliability,
or
operation.
ELECTRICALSHOCK
HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical
disconnect
switch
must
be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
EXPLOSION
HAZARD
Failure to follow this warning could
result in death, serious personal injury,
and/or property damage.
Never
use air or gases containing
oxygen for leak testing or operating
refrigerant compressors.
Pressurized
nfixtures of air or gases containing
oxygen can lead to an explosion.
EQUIPMENT
DAMAGE HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
Do not bury more than 36 in. (914 ram) of refrigerant pipe
in the ground. If any section of pipe is buried, there must be
a 6 in. (152 ram) vertical rise to the valve connections on
the outdoor units. If more than the recommended length is
buried, refrigerant may nfigrate to the cooler buried section
during extended periods of system shutdown. This causes
refrigerant
slugging
and
could
possibly
damage
the
compressor at start-up.
SYSTEM
REQUIREMENTS
Allow
sufficient
space
for airflow
and servicing
unit.
See
minimum
required
distances
between
unit and walls or
ceilings,
Recommended
Connection
Method for Power and Communi-
cation
Wiring
(To minimize
communication
wiring
interfer-
ence)
Power
Wiring:
The main power
is supplied
to the outdoor
unit. The field supplied
connecting
cable from the outdoor
unit to indoor
unit consists
of
three (3) wires
and provides
the power
for the indoor
unit. Two
wires are high voltage
AC power
and one is a ground
wire.
Consult
your
local
building
codes
and
the
NEC
(National
Electrical
Code)
or CEC
(Canadian
Electrical
Code)
for special
requirements.
All wires
must
be sized
per NEC
or CEC
and local
codes.
Use
Electrical
Data
table
MCA
(minimum
circuit
amps)
and MOCP
(maximum
over current
protection)
to correctly
size the wires
and
the disconnect
fuse or breakers
respectively.
Per caution
note, only copper
conductors
with a minimum
300 volt
rating and 2/64-inch
thick insulation
must be used.
Communication
Wiring:
A separate
shielded
copper
conductor
only, with
a minimum
300
volt rating
and 2/64-inch
thick insulation,
must
be used as the
communication
wire from the outdoor
unit to the indoor
unit.
To nfininfize
voltage
drop
of the control
wire, use the following
wire size and maximum
lengths
shown
in the chart below:
Wire Size
Length
ft (m)
18 AWG
50 (15)
16 AWG
50 (15) to 100 (30)
EQUIPMENT
DAMAGE HAZARD
Failure to follow
this caution may result in equipment
damage or improper operation.
• Wires should be sized based on NEC and local codes.
• Use copper conductors only with a minimum 300 volt
rating and 2/64 inch thick insulation.

Advertisement

Table of Contents
loading

Table of Contents