Carrier 38GJ Owner's Manual & Installation Instructions page 16

Multi-zone ductless split system sizes 30 to 42
Table of Contents

Advertisement

38GJQG36---3,38GJQG42---3
r
1
i
OUTDOORUNI T
Ii XT
XT1
XT2
XT3
XT4
XT5 I
N(1)
2
3
N(1) 2
3
N(1) 2
3
N(1) 2
3
N(1) 2
3
1
--_
PE
_)
PE
PE
PE
PE
PE
POWER i INDOORUNIT A I
INDOOR UNIT B
i INDOOR UNIT C ii INDOOR UNIT D I
INDOOR UNIT E I
Fig 12
4.4.2 Grounding Require ments
(1) The air conditioner is classified as a Class I appliance, so its grounding must be reliable.
(2) The yellow-green
line of the air conditioner is the earth line and can not be used for any other purpose, cut off or
fixed by the tapping screw; otherwise it would cause an electric shock.
(3) A reliable ground terminal should be provided and the ground wire can not be connected to any of the following
items:
@Running
water pipe
@Coal gas pipe @Sewage
pipe @Other places where the professional personnel
think unreliable.
4.4.3 Electrical
Cable
Connection
A CAUTION
1)
A mistake connecting
the line will result in a malfunction.
After the electrical wiring is working,
ensure
the wire
between the connection place and the fixed place has a certain amount of space.
2)
The connection piping and connection line of each indoor unit should connectwell
according to the instruction.
3)
The electric installation should be carried out by a technician
instructed in the local laws, regulations
and
this manual.
4)
The installation location should be dry, shielded from direct sunlight or strong winds.
5)
Install a breaker in the circuit that can shut off the system's main power supply. Also install an air
switch coupled with the leakage current protection switch must be equipped.
4.4.4 Wiring of the Power
Cord
(1). Open the side plate.
(2). Connect the power cord to terminals
"L1 ", "L2"
and the earthing bolt. Next, connect the wiring
terminals
"N(1),2,3"
of the indoor unit to the corresponding
outdoor unit terminals.
(3). Fix the power cordwith
wire clips.
(4). Place the power cord through the rubber ring.
,A,CAUTION
If the supply cord is damaged,
it must be replaced
by the manufacturer
or its service agent or a similarly
qualified person to avoid a hazard.
16

Advertisement

Table of Contents
loading