3 Electrical Data - Daikin MXS-FV1B_F2V1B User Manual

Multi application inverter controlled
Table of Contents

Advertisement

3
Electrical data
Model
H/P
Outdoor
C/D
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (See note 6). (A)
MSC
: MSC means the max. current during the starting of
compressor. (A)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output (W)
• Outdoor Units • R410A • MXS-FV1B_F2V1B
Units
Hz
Volts
Min.
1. RLA is based on the following conditions:
Cooling
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is
not below or above listed operation range limits
3. Maximum allowable voltage variation between phases is 2%
4. MCA represents maximum input current.
MFA represents capacity which may accept MCA
5. Select wire size based on the larger value of MCA.
6. MFA is used to select the circuit breaker and the ground fault circuit interrupter
(earth leakage circuit breaker)
7. For more details concerning conditional connections, see
http://extranet.daikineurope.com, select ''E-Data Books''. Finally, click on the document title
of your choice.
• Split Sky Air • Outdoor Units
Power supply
Max.
MCA
MFA
NOTES
Comp.
OFM
MSC
RLA
W
3
FLA
1
3
3D056163
10