Content
ODF-MN-B-C-R/T
Figure 89 Example of a label on an optical fiber between the device and the ODF
ODF-G01-01-01-R—The local end of the optical fiber is connected to the optical receiving
terminal on Row 01, Column 01 of the ODF in Row G Column 01 in the equipment room.
A01-01-05-05-R—The peer end of the optical fiber is connected to Optical Receiving
Interface 5 on Slot 05, Chassis 01 in the cabinet on Row A, Column 01 in the equipment
room.

Engineering labels for DC power cords

These labels are affixed to DC cords that provide power for racks, and the protection grounding
cables including the –48V, PGND, and BGND cables. The labels for DC power cords are affixed to
one side of the identification plates on cable ties.
Meaning
B—Chassis number
C—Slot number
D—Fiber port number
R—Optical receiving interface
T—Optical transmitting
interface
MN—Row number and column
number of ODF
B—Row number of the terminal
device
C—Column number of the
terminal device
R—Optical receiving interface
T—Optical transmitting
interface
134
Example
Numbered in bottom-up order with two digits,
for example, 01.
Numbered in top-down and left-right order
with two digits, for example, 01.
Numbered in top-down and left-right order
with two digits, for example, 05.
N/A
M—Row number of the rack in the
equipment room, in the range of A to Z.
N—Column number of the rack in the
equipment room, in the range of 01 to
99.
For example, G01 is the ODF of Row G and
Column 01.
In the range of 01 to 99, for example, 01-01.
N/A