Introduction

1.0: Scope

This section is a general description of the Power-Sure
T800R/T800P/T800F power conditioners . It includes
receiving, electrical, environmental, mechanical
specifications, and cabinet standard dimensions .

1.1: Section descriptions

This manual is divided into three sections:

Section 1: Introduction

This section is a general description of the Power-Sure
T800R/T800P/T800F power conditioners . It includes
receiving, electrical, and mechanical specifications
and cabinet measurements .
Section 2: Installation
This section guides the user through installation
requirements, wire and circuit diagrams, hardwire
connections, and factory configuration ratings for the
Power-Sure T800R/T800P/T800F .
Section 3: Maintenance
This section contains preventive maintenance for the
Power-Sure T800R/T800P/T800F and a troubleshooting
guide to assist the user with any communication and
configuration connections .

1.2: Receiving

Before accepting shipment from the freight carrier, inspect
the exterior surfaces of all shipping containers or packaging
used and the equipment for damage that may have
occurred during transit . If the shipping containers or
equipment shows evidence of damage, note the damage
on the receiving document (bill of lading) prior to signing
for receipt of equipment .
All claims for shipping damage must be filed directly
with the carrier. Replacements for damaged components
should be ordered through Eaton .
Check by thorough inspection if any electrical connections
have become loose because of vibration during shipment .
Check the nameplate to be sure that the voltage and
frequency match the available power supply . Under no
circumstance should the unit be connected to a power
source that does not conform to the nameplate rating .
Instruction manual—single-phase power conditioners IM01002005E September 2015 Eaton.com

1.3: Location and storage

The unit has been completely inspected and extensively
tested under various load conditions prior to shipment .
Installing it at a proper location will ensure long trouble-free
operation . T800R models are forced-air cooled with the air
intake on the sides of the enclosure . Air exhausts are at the
rear of the enclosure . Therefore, it should be installed in a
clean, dry place with enough clearance to allow a free flow
of air . Allow at least four inches of space between the unit
and the wall or other equipment for portable units . Allow
enough space for maintenance on all four sides on larger
units, and unrestricted air exhaust from the fan . Never
mount T800P models one unit over the other or near
a heat source . Heat rising into or blowing into the unit
may cause premature failure .
If the equipment is to be stored prior to installation, it
should be stored in a cool, dry, well-ventilated location that
is protected from rain, splashing water, chemical agents,
etc . The equipment should be covered with a tarpaulin or
plastic wrapper to protect it against dust, dirt, paint, or other
foreign materials .

1.4: Prerequisites to installation

An efficient installation depends on careful planning and site
preparation . Installation of the equipment must be handled
by skilled technicians and electricians familiar with the
special requirements of high-voltage electrical equipment .
The installation must comply with the requirements of the
National Electrical Code (ANSI/NFPA 70, latest issue) and
local codes as applicable .
Startup service is offered by Eaton . Do not allow
unqualified personnel to handle, install, or operate
Power-Sure 800 power conditioners .

1.5: General description

The Power-Sure 800 is a state-of-the-art ferroresonant
isolation transformer . Its all-passive electronic design
provides unsurpassed reliability and power conditioning
performance . The overall function of the Power-Sure 800
is to receive raw, extremely polluted electrical power and
purify it for use by sensitive electronic equipment . This
highly reliable product is ideal for heavy industrial
applications where high power equipment constantly
interferes with a building's electrical system . Use the
Power-Sure 800 where isolated, regulated, transient,
and noise-free sinusoidal power is required .
Ferroresonant, copper coils, dry type, convection cooled,
600 V class, 200 ºC system .
Core uses M-6 grade, grain-oriented, stress-relieved
transformer steel .
Transformers are vacuum impregnated with epoxy resin .
NEMA Type 1, general purpose, indoor enclosure .
Heavy gauge steel . Base substructure adequate
for fork lifting .
Introduction
1