Input Volts And Amps Specifications 500 Va-5 Kva - Eaton T800R-00500 Instruction Manual

Power-sure 800
Table of Contents

Advertisement

Installation
2.4: Input volts and amps specifications 500 VA–5 kVA
Full kVA ratings may be used at 120 Vac on secondary windings (X1–N or X3–N) .
Table 2-1: Input volts and amps specifications 500 VA–5 kVA
Power rating
Model
500 VA
T800P-00500
750 VA
T800P-00750
1 kVA
T800P-01000
1.5 kVA
T800P-01500
2 kVA
T800P-02000
3 kVA
T800P-03000
5 kVA
T800
P = wall-mounted; F = floor-mounted .
a
Note: Recommended input circuit breaker should be sized 125% of stated input amperage .
Input
120V H1–H2
●●
208V H1–H3
●●
240V H1–H4
●●
480V H1–H5
●●
Terminals
#8 stud
●●
Maximum wire size: 10 AWG
● ●
Recommended torque: 15 lb in
● ●
Figure 2-9: Hardwiring for 500 VA–5 kVA units
18
Instruction manual—single-phase power conditioners IM01002005E September 2015 Eaton.com
120 V
4.6 A
6.9 A
9.2 A
13.7 A
18.3 A
27.5 A
-05000
45.8 A
a
208 V
2.6 A
3.9 A
5.3 A
7.9 A
10.5 A
15.8 A
26.4 A
Output
120V X1–N
●●●●●
208V X1–X2
●●●●●
240V X1–X3
●●●●●
120V X3–N
●●●●●
#10 stud
●●●●●
Maximum wire size: 6 AWG
● ●●●●
Recommended torque: 20 lb in
● ●●●●
240 V
480 V
2.3 A
1.1 A
3.4 A
1.7 A
4.6 A
2.3 A
6.8 A
3.4 A
9.2 A
4.6 A
13.7 A
6.9 A
22.9 A
11.4 A

Advertisement

Table of Contents
loading

Table of Contents