2.5: Input volts and amps specifications 8–25 kVA
Full kVA ratings may be used at 120 Vac on secondary windings (X1–N or X3–N) with exception of 20 kVA and 25 kVA units,
in which case 120 Vac loads (X1–N or X3–N) should not exceed 50% of the unit's rated power .
Table 2-2: Input volts and amps specifications 8–25 kVA
Power rating
8 kVA
10 kVA
15 kVA
20 kVA
25 kVA
P = wall-mounted; F = floor-mounted .
a
Note: Recommended input circuit breaker should be sized 125% of stated input amperage .
Input
208V H1–H2
●●
240V H1–H3
●●
480V H1–H4
●●
Terminals
Wire range: 10–1/0 AWG
●●
Recommended torque: 45–50 lb in
●●
Figure 2-10: Hardwiring for 8–25 kVA units
Model
T800
-08000
a
T800
-10000
a
T800F-15000
T800F-20000
T800F-25000
Instruction manual—single-phase power conditioners IM01002005E September 2015 Eaton.com
208 V
42 A
53 A
80 A
106 A
132 A
Output
120V X1–N
●●●●●
208V X1–X2
●●●●●
240V X1–X3
●●●●●
120V X3–N
●●●●●
Installation
240 V
37 A
46 A
70 A
92 A
115 A
480 V
18 A
23 A
34 A
46 A
57 A