Eaton E02A User Manual
Eaton E02A User Manual

Eaton E02A User Manual

Integrated rack type air conditioner

Advertisement

Quick Links

Eaton Micro Data Center
E02A Integrated rack type air conditioner
User manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E02A and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton E02A

  • Page 1 Eaton Micro Data Center E02A Integrated rack type air conditioner User manual...
  • Page 2 Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
  • Page 3: Table Of Contents

    5.9 Reinstall the air conditioner into the cabinet ........... . .17 E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 4: Introduction

    If the measures described in the following are not strictly observed material damage may be caused. Air conditioner description The integrated rack type air conditioner is a cooling product developed for the Eaton iCUBE micro data center. This air conditioner’s frequency can be regulated. It has cooling capacity regulating function, and the fans can regulate speed automatically.
  • Page 5: Operating Conditions

    Environmental conditions existing in the application of electric and electronic product – Storage GB4798.2 Environmental conditions existing in the application of electric and electronic product – Transportation GB4798.3 Environmental conditions existing in the application of electric and electronic product – Use E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 6: Safety Notices

    Losses from the components installed in the enclosure must not exceed the specific refrigeration capacity of • the air conditioner itself; The user must not modify the air conditioner in any way. • Figure 2 Distance Diagram E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 7: Installation And Operation

    CAUTION! Too high voltage may lead to damage of cabinet air conditioner. Please follow the voltage requirement marked on the nameplate to switch on the air conditioner. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 8 Hydrogen discharge / emergency fan dry contact (COM) (Option) Door open alarm input (option) Door open alarm input (option) communication ports RS485 communication ports (+) (Option) RS485 communication ports (-) (Option) E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 9: Power-On Steps

    Firstly make sure the AC voltage is in accordance with the standard, and then close the power input switch. 30s later the internal cycle fan of the unit will be started. After delay time about 3min, the unit select operation mode according to the unit’s. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 10: System Function Introduction

    Cool T: Temperature control sensitivity. CAUTION! For the reliable operation of the unit and the maximum energy efficiency, it is recommended that the users should not randomly change the temperature set point. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 11: Component Control Mode

    5. The compressor runs for 60 seconds with upper limit speed, meanwhile the external fan runs with full speed. 6. If configured with heater, starts heater and runs for 120s. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 12: Hydrogen Discharging/Emergency Fan (Option)

    Cabinet Temp Sensor Failure Temp sensor failure Only send alarm Evaporator Temp Sensor Failure Temp sensor failure Only send alarm Condenser Temp Sensor Failure Temp sensor failure Only send alarm E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 13: Unit Menu Structure

    4.8.2 Menu structure : Left button, which is used to select the previous bit of the data. : Right button, which is used to select the next bit of the data. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 14 Tp: Evaporator coil temperature sensor Te: Compressor exhaust pipe temperature sensor Cond: Condenser coil temperature sensor Unit menu structure otee: This diagram is unit menu structure, not the real factory setting. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 15: Maintenance

    Check whether there is foreign matter blocking the fan. Internal return Temp. is too low Check whether the internal return Temp. is lower than the internal fan stop point. If so, the internal fan will stop. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 16: Charge Refrigerant

    Phillips screwdriver is used to remove screws from other parts. • Diagonal pliers Used to process cables on site and remove the fixed cable ties. Portable vacuum pump For eye protection E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 17 Refrigerant R410A refrigerant. Electronic scale Used to charge refrigerant and monitor the weight of the refrigerant charged. Wear gloves when charging refrigerant and vacuuming. Protective gloves Goggles For eye protection E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 18: Disassemble The Unit

    Use a pressure gauge to connect the high-pressure charging port (red pipe) and low-pressure charging port (blue pipe) of the air conditioner, and the middle pipe is connected to the vacuum pump. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 19 4. After the refrigerant charging is completed, close the valve on the low pressure port side of the pressure gauge, do not remove the pipeline connection for the time being, and perform the power-on operation and refrigeration operation. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 20: Power On And Test The Air Conditioner

    Then install the install the air conditioner in the reverse order. E02A INTEGRATED RACK TYPE AIR CONDITIONER UM.ICUBE2.0-IRTAC.SG.0822 August 2022 www.eaton.com...
  • Page 21 Photos and pictures also do not warrant a specific layout or functionality. Their use in whatever form is subject to prior approval by Eaton. The same applies to Trademarks (especially Eaton, Moeller, and Cutler-Hammer). The Terms and Conditions of Eaton apply, as referenced on Eaton Internet pages and Eaton order confirmations.

Table of Contents