Siemens 7PG21 Solkor Rf Technical Manual page 20

Feeder protection
Table of Contents

Advertisement

Supervision supply fail
relay (B22)
Receive Repeat Relay
Timing
B74 Repeat Element
Delay on drop off 400ms+-10%
4.3 Injection Intertripping
Rating Vx, 110-125V dc
Burden 1A at 125V dc full output
400mA with economy resistor
5 Environment
5.1 Temperature
IEC 60068-2-1/2
Type
Operating range
Storage range
5.2 Humidity
IEC 60068-2-3
Type
Operational test
5.3 IP Ratings
Type
Installed with cover on
Installed with cover removed
6 Mechanical Durability
Vibration, relays comply with BS142 section 2.1 Category S2.
Shock, relays withstand 20G shock or impact on the panel without operating
Operation/mechanical life, relays will withstand in excess of 10,000 operations.
©2010 Siemens Protection Devices Limited
Hand Reset Flag
Self Rest Flag
Level
-10 °C to +55 °C
-25 °C to +70 °C
Level
56 days at 40 °C and 95 % relative humidity
Level
IP 51
IP 30
7PG21 Solkor Rf Performance Specification
Chapter 2 Page 5 of 5