1 LOCATION
Do not flue into natural draught flues or
fireplaces, this unit can only be used with
a Rinnai flue kit.
(A flue kit is available to flue right through
to the rear of most fueplaces.
Use this kit
when the heater is going to be installed in
front of a fireplace.)
Do not flue unit into other rooms.
Flue terminal must be outside.
Flue may be positioned
directly under
opening windows, with a minimum clear-
ance of 150 mm.
Flue sizes:
4 flue lengths are available.
A flue suits walls 115-240 mm
B flue suits walls 240400 mm
C flue suits walls 400-600 mm
D flue suits walls 600-800 mm
For information
on special extra long
flues, contact Rinnai.
Co-ax internal wall flues are also available.
Separate
instructions
are supplied with
co-ax flue kits.
W Standard installation of flue manifold.
Diagram below shows minimum clearances
and distances from obstructions.
Also check AG601 and/or local regula-
tions.
I PZA I
Side Clearances.
-
13-