Noise Filter for Signal cables

Provide all the cables (power supply cable, motor cable, encoder cable, interface cable) with the noise filter for
signal cable.
Grounding
(1) Don't fail to connect the servo driver protective earth terminal (
panel together.
(2) When connecting to the protective earth terminal (
provided.

Leakage Breaker

Connect Type-B leakage breaker (RCD) to the primary power supply of the servo driver.
Driver and Peripheral Devices Applied Thereto (EC Directives)
For the detail refer to "System Configuration and Wiring", Page 26.
Install the noise filters in reference to DV0P4160 (page 182).
Conformance to UL Standards
The noise filters conform to UL508C (File No. E164620) to satisfy the following conditions.
(1) The servo driver should be used under Contamination Level 2 or 1 specified by IEC60664-1 (housing the driver
in an IP54 control box).
(2) Install a circuit breaker or fuse between the power supply and noise filter. The circuit breaker or fuse should be
a UL listed mark (
) type.
The current rating of the circuit breaker or fuse should be per the table in page 26.
Option Part No.
Manufacturer's part No.
DV0P1460
Weight: 62.8 g
) and the protective earth plate of the control
), avoid co-clamping. Two protective earth terminals are
183
[Reference]
Manufacturer
ZCAT3035-1330
TDK Co., Ltd.