Replacing A Fan Assembly; Removing An Environmental Service Module - IBM DCS3860 Installation, User's, And Maintenance Manual

Hide thumbs Also See for DCS3860:
Table of Contents

Advertisement

Release
levers
Figure 54. Removing an environmental service module
3. Slide the ESM out of the bay and set it aside.
4. Ensure that the release levers on the ESM are in the open position.
5. Slide the ESM into the bay until it stops.
6. Close the release levers.
7. Connect the SAS cables to the ESM.
8. Turn on the power.
9. Go to http://www.ibm.com/servers/storage/support/ to check for ESM code

Replacing a fan assembly

Before you begin, ensure that you wear an anti-static wrist strap.
Complete the following steps to replace a failed fan assembly. To preserve the
optimal airflow, do not remove a failed fan assembly FRU from the storage
expansion enclosure until you are ready to replace it with a new FRU.
CAUTION:
To prevent damage from overheating, replace a failed fan assembly FRU within
5 minutes of removal. If replacing it will take longer than 5 minutes, stop all I/O
activity to the storage expansion enclosure and turn off the power until you
complete the replacement.
108
IBM System Storage DCS3860 Storage System: Installation, User's, and Maintenance Guide
I
O
D C
A C