Siemens RUGGEDCOM RS910 Installation Manual page 35

Hide thumbs Also See for RUGGEDCOM RS910:
Table of Contents

Advertisement

RUGGEDCOM RS910
Installation Guide
Test
IEC 60255-5
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RS910 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
EMI and Environmental Type Tests
Description
Dielectric Strength
HV Impulse
IEEE 1613
Clause
9
ESD
8
Radiated RFI
7
Fast Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
Description
Cold Temperature
Dry Heat
Signal ports
2 kVAC (Fail-Safe Relay output)
DC Power ports
AC Power ports
Signal ports
5 kV (Fail-Safe Relay Output)
DC Power ports
AC Power ports
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Levels
1.5 kVDC
2 kVDC
5 kV
5 kV
Test Levels
+/- 8 kV
+/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Test Levels
Severity Levels
Chapter 6
Certification
Severity Levels
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents