Allen-Bradley 2080-IQ4 User Manual page 73

Micro800 plug-in modules
Table of Contents

Advertisement

Rockwell Automation Publication 2080-UM004C-EN-E - March 2015
Output Specifications – 2080-OF2
Attribute
(1)
Step Response to 63%
Current Load ln voltage output, max
Resistive load on current output
Load range on voltage output
Max. inductive load
(current outputs)
Max. capacitive load
(voltage outputs)
(2)
Overall Accuracy
Non-linearity (in percent full scale)
(3)
Repeatability
(in percent full scale)
Output error over full temperature range,
-20...65°C (-4...149°F)
Open and short-circuit protection
Output overvoltage protection
Input group to bus isolation
Channel to channel isolation
Temperature, operating
Temperature, non-operating
Relative humidity
Operating altitude
Cable length, max.
(1) Step response is the period of time between when the D/A converter was instructed to go from minimum to full
range until the device is at 63% of full range.
(2) Includes offset, gain, non-linearity and repeatability error terms.
(3) Repeatability is the ability of the output module to reproduce output readings when the same controller value is
applied to it consecutively, under the same conditions and in the same direction.
Specifications Appendix A
2080-OF2
5 ms
10 mA
0...500 Ω (includes wire resistance)
> 1k Ω @ 10V DC
0.01 mH
0.1 µF
Voltage Terminal: ±1% full scale @ 25 °C
Current Terminal: ±1% full scale @ 25 °C
± 0.1%
± 0.1%
Voltage: ± 1.5%
Current: ± 2.0%
Yes
Yes
No isolation
Non-isolation
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4...149 °F)
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40...185 °F)
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing
2000 m
10 m
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents