3.12 Malfunctions

3.12.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistors:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
3.12.2 Detection of Overcurrent and Overload
Outline
An excessive output current is detected and the OL temperature is observed to protect the
compressor.
Detail
3.12.3 Refrigerant Shortage Detection
Detecting by power consumption
If the power consumption is below the specified value and the frequency is higher than the
specified frequency, it is regarded as refrigerant shortage.
The power consumption is low comparing with that in the normal operation when refrigerant is
insufficient, and refrigerant shortage is detected by checking power consumption.
Refer to page 69 for detail.
Function and Control
If the OL (compressor head) temperature exceeds 120°C, the system shuts down the
compressor.
If the inverter current exceeds 9.25 ~ 10 A (depending on the model), the system shuts down
the compressor.
Refrigerant shortage zone
50 ~ 55 Hz
Frequency
(depending on
the model)
(R21198)
Control Specification