Control Specification; Mode Hierarchy; Frequency Control - Daikin FTXM-K Series Service Manual

Inverter pair
Table of Contents

Advertisement

SiBE041434E

3. Control Specification

3.1

Mode Hierarchy

Outline
The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Detail
Note:
Unless specified otherwise, a dry operation command is regarded as cooling operation.
3.2

Frequency Control

Outline
The compressor frequency is determined according to the difference between the room
thermistor temperature and the target temperature.
Function and Control
Air conditioner control mode
Forced operation mode
Power transistor test mode
Normal operation mode
When the shift of the frequency is less than zero (∆F<0) by PI control,
the target frequency is used as the command frequency.
Upper limit frequency
Command frequency
Limit frequency
Lower limit frequency
Initial frequency
PI control
Defrost control
Forced cooling operation (for pump down operation)
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating operation
Discharging from capacitor
Stop
Input current control, etc.
FMAX
Skip control
FMIN
Four way valve operation compensation, etc.

Control Specification

(R19522)
Dropping function
Upper limit function
Compressor protection function
Target frequency
Lower limit function
(R18023)
38