Check; Thermistor Resistance Check - Daikin FTXM-K Series Service Manual

Inverter pair
Table of Contents

Advertisement

Check

5. Check

5.1

Thermistor Resistance Check

Check No.01
Disconnect the connectors of the thermistors from the PCB, and measure the resistance of
each thermistor using a multimeter.
97
The data is for reference purpose only.
Thermistor temperature (°C)
–20
–15
–10
–5
0
5
10
15
20
25
30
35
40
45
50
Room temperature thermistor
of 20/25 class models
(kΩ)
50
25
0
–15
15
0
When the room temperature thermistor is soldered on a PCB, remove the PCB from the
control PCB to measure the resistance.
When the connector of indoor heat exchanger thermistor is soldered on a PCB, remove the
thermistor and measure the resistance.
Resistance (kΩ)
Room temperature thermistor
of 20/25 class models
73.4
57.0
44.7
35.3
28.2
22.6
18.3
14.8
12.1
10.0
8.2
6.9
5.8
4.9
4.1
(R25°C = 10 kΩ, B = 3435 K)
(kΩ)
150
100
50
–15
30
45
(˚C)
Resistance range
Other thermistors
197.8
148.2
112.1
85.60
65.93
51.14
39.99
31.52
25.02
20.00
16.10
13.04
10.62
8.707
7.176
(R25°C = 20 kΩ, B = 3950 K)
Other thermistors
0
15
30
45
Room temperature
thermistor
Multimeter
Multimeter
(R21542)
Service Diagnosis
SiBE041434E
(˚C)
(R11952)
(R20505)