Download Print this page
TemperZone ISD 220Q Installation & Maintenance

TemperZone ISD 220Q Installation & Maintenance

Ducted split system indoor units

Advertisement

Quick Links

ISD 220Q, 265Q
Ducted Split System
Indoor Units
Fig. 1
Dimensions (mm)
Not to Scale
SPRING MTG CTRS
HANGING CENTRES
80
595
OPTIONAL
SPRING MTG
CENTRES
530
HANGING
CENTRES
165
ACCESS
PANEL
A
OVERALL
MODEL
A
B
C
ISD 220Q
425
15
350
ISD 265Q
555
85
500
Fig. 2 Spring Mounting
RECOMMENDED
MOUNTING
SYSTEM
(OPTIONAL
EXTRA)
1285
1240
1185
REFRIGERANT
CONNECTIONS
MOUNTING
SLOTS 20 x 9
865
ELECTRICAL
CONDUIT HOLES
230
1365
OVERALL
NOTE
Net Weight
The manufacturer reserves the right to change
specifications at any time without notice or
74 kg
obligation. Certified dimensions available on
93 kg
request.
Fig. 3 Solid Mounting
ISD 220Q, 265Q
PROJECTION
FAN ACCESS VIA
REMOVEABLE BASE
& DRAIN TRAY
ELECTRICAL
ACCESS PANEL
60
60
15
B
DRAIN 19 OD
630 OA
MOUNTING ROD
MOUNTING FLANGE
TIGHTEN
LOCKNUTS
FOR
STRENGTH
Installation &
Maintenance
GENERAL
The ISD 220Q indoor units are designed to
be coupled with the OSA 220 outdoor units.
The ISD 265Q indoor units are designed to
be coupled with the OSA 265 outdoor units.
Units must be installed in accordance with
all national and local safety codes.
Options
1. Filter Box.
2. Spring Mounting Kit
3. Electric Heater Box.
FILTER BOX (Option)
The Filter Box is installed by unscrewing
the return air spigot and replacing it with
the Filter Box's filter-integrated spigot. The
filter may be accessed from either side of
this spigot. This new spigot has a depth of
135 mm, instead of 60 mm.
ELECTRIC HEATER BOX (Option)
The Electric Heater Box is installed by
C
unscrewing the supply air spigot and
replacing it with the Electric Heater Box's
element-integrated spigot. This new spigot
has a depth of 195 mm, instead of 60 mm.
A separate page of installation instructions
is supplied with the Kit.
UNPACKING UNITS
In an area adjacent to the installation site
remove from the ISD unit from its carton
and examine it carefully for any damage
which may have occurred in transit. Record
any damage on the carrier's delivery
documents and refer the matter
immediately to the manufacturer's nearest
Sales Office.
INSTALLATION
Positioning & Mounting
Provide 500 mm minimum clearance to the
electrical panel. If the filter box option is to
be used, allow adequate clearance for the
two half length filters to be withdrawn from
either side of the unit.
If the Electric Heat Kit option is to be used,
allow adequate clearance for servicing.
If low noise is a critical factor in the
installation, refer to Figure 6 for noise
isolation recommendations.
It is recommended that the unit be mounted
using the spring mounting system, supplied
as an optional extra (Fig.2). This system
minimises transfer of vibration into the
building structure.
If a more rigid installation can be tolerated,
then suspend the unit from four threaded
rods (not supplied) and use locknuts (not
supplied), as shown in Figure 3.

Advertisement

loading

Summary of Contents for TemperZone ISD 220Q

  • Page 1 Maintenance Fig. 1 Dimensions (mm) ISD 220Q, 265Q GENERAL The ISD 220Q indoor units are designed to Not to Scale PROJECTION be coupled with the OSA 220 outdoor units. The ISD 265Q indoor units are designed to be coupled with the OSA 265 outdoor units.
  • Page 2: Condensate Drain

    The electrical supply required (via the above the unit drain tray. (Refer Fig.4). THERMOSTATS Outdoor Unit) is specified on the Outdoor For options, refer to the temperzone For long condensate pipe runs, fit a vent Unit's wiring diagram. pamphlet 'ISD 73Q-300Q - Approved pipe near the drain trap.
  • Page 3 4. If generous duct size is not possible, use turning vanes on bends to reduce air turbulence (regenerated noise). 5. Use 90° bends in ducting to significantly assist in noise reduction. Wiring ISD 220Q NOTE The manufacturer reserves the right to change specifications at any time without notice or obligation.
  • Page 4 Wiring ISD 265Q This pamphlet replaces the previous issue no. 2165 dated 11/02. ISD 220Q wgt, wiring revisions B & A. © temperzone limited 2003 06/03 Pamphlet No. 2230...

This manual is also suitable for:

Isd 265q