Reference Section
Connections on 11-Series Expansion I/O Module
Terminal block TB1 and the input mode jumpers are mounted on the option module installed in the drive.
11-Series I/O Module
Table 18 - Analog Input Mode Jumpers
Voltage Mode
1
1
P4
P5
2
2
Table 19 - TB1 Terminal Designations
Terminal Name
–10V
–10 Volt Reference
10VC
10 Volt Common
+10V
+10 Volt Reference
Sh
Shield
–10V
10VC
+10V
Ao0–
Analog Out 0 (–)
Sh
Ao0–
Ao0+
Ao0+
Analog Out 0 (+)
Sh
Ai0–
Ai0+
Sh
Shield
Sh
Di0
Di0P
Di1
Di1P
Ai0–
Analog Input 0 (–)
Di2
Di2P
Ip
Ai0+
Analog Input 0 (+)
Ic
EnC
EnNO
Sh
Shield
Di0
Digital Input 0
Di0P
Digital Input 0 Power
Di1
Digital Input 1
Di1P
Digital Input 1Power
Di2
Digital Input 2
Di2P
Digital Input 2 Power
Ip
Input Power
Ic
Input Common
EnC
Enable Output
EnNO
(1) Digital Inputs are either 24 Volts DC (1132C) or 115 Volts AC (1132D) based on module catalog number. Ensure applied voltage is
correct for I/O module.
(2) Differential - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
(3) For CE compliance use shielded cable. Cable length should not exceed 30 m (98 ft).
(4) I/O Module parameters also have a Port designation.
44
Current Mode
1
1
P4
P5
2
2
Description
Negative 10V DC for analog inputs. 2k ohm minimum.
For (–) and (+) 10 Volt references.
Positive 10V DC for analog inputs. 2k ohm minimum.
Terminating point for wire shields when an EMC plate
or conduit box is not installed.
Bipolar, ±10V, 11 bit & sign, 2 k ohm minimum load.
4-20 mA, 11 bit & sign, 400 ohm maximum load.
Terminating point for wire shields when an EMC plate
or conduit box is not installed.
(2)
Differential
, bipolar, 11 bit & sign.
Voltage Mode: ±10V @ 88k ohm input impedance.
Current Mode: 0-20 mA @ 93 ohm input impedance.
Terminating point for wire shields when an EMC plate
or conduit box is not installed.
24V DC (30V DC Max.) - Opto isolated
(1)
High State: 20...24V DC 11.2 mA DC
Low State: 0...5V DC
(3)
120V AC (132V AC Max.) 50/60 Hz
(1)
High State: 100...132V AC
Low State: 0...30V AC
(1)
External 24V DC or 115V AC power supply input
connections. Does not power the main control board.
ATEX fault enable output. Used only when an ATEX
option module is installed.
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Related
(4)
Param
75
on Port X
50, 70
on Port X
1
on Port X
- Opto isolated
Need help?
Do you have a question about the PowerFlex 753 and is the answer not in the manual?