CS-F24DB4E5 CU-L24DBE5 / CS-F28DB4E5 CU-L28DBE5
Earth lead wire shall be longer than other lead wires as shown in the figure for the electrical safety in case of the slipping out of the
cord from the anchorage.
• • • • Power supply specifications
Model name
CU-L24DB***
220V-240V~
CU-L28DB***
220V-240V~
CU-L34DB***
220V-240V~
CU-L43DB***
220V-240V~
CU-L50DB***
380V-415V
3N~
NOTE
1. Where ground work (earth) is carried out, do not connect the ground return to the gas pipe, water line pipe, grounded circuit of the
telephone and lightning rod, or ground circuit of other product in which earth leakage breaker is incorporated. (Such action is
prohibited by statute, etc.)
Make sure the indoor and outdoor connection wires are detangled. (There might be effect to received outside noise.)
2. Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR) rating
specifications) or use the cables based on IEC standard. (245IEC57, 245IEC66)
3. Select the particular size of electrical wire for power supply cables in accordance with the standards of the given nation and
region.
Leakage
Circuit breaker
current
(Minimum Capacity)
breaker
Switch
Fuse
(A)
(A)
(A)
30
30
20
30
30
20
40
40
30
40
40
40
30
30
30
2
Minimum
4mm
Maximum
power
cable
permissible
impedance
supply
based on
cables
length (m)
14
2
4 mm
14
9
8
11
56
Indoor/outdoor
unit connection
power cables
(Ω)
(terminals
,
,
0.1
2
2.5 mm
× 3
0.1
0.05
0.05
0.02
,
)