(1) Choose the appropriate operation block area by the difference between room temperature and thermostat setting temperature as
shown below.
·
Operation block area
D block
Room temp. – Setting temp.(deg)
(2) Start up operation
C.D block
Compressor
ON
and
OFF
outdoor fan
Speed 4
Speed 1
Indoor fan
OFF
0
Start
Note (1) Thermostat operation is performed in A, B block. When compressor and indoor fan stop by thermostat operation within 12 minutes from start, temperature
check is performed by operating indoor fan at speed 1 for 20 seconds before finishing 12 minutes and allowing decision of next operation block.
(3) Dry operation
After finishing start up operation described in (2) above, dry operation is performed at 8 minutes intervals, according to the
difference between room temperature and thermostat setting temperature as shown below.
Beside, 1 cycle of this operating time consists of 8 minutes, 7 cycle operation is performed then.
D block
Compressor
ON
and
OFF
outdoor fan
Speed 1
Indoor fan
OFF
0
Start
B block
Compressor
ON
and
OFF
outdoor fan
Speed 4
Speed 1
Indoor fan
OFF
0
Start
(4) ECONOMY operation ( "ECONO" button on the remote control : ON)
The set temperature changes as shown at right, and the