One or two PDSs can be configured, except for a lineup with a
SuperNode-based cabinet, in which case one PDS is configured at shelf
position 30. Configuration of PDS shelves varies according to the types of
Meridian SL-100 frames to which the CPDC provides power.
A DC breaker panel is available and contains a total of 42 circuit breakers
(21 on each of the A and B buses). Capacitive filtering of each bus is
provided on the breaker panel and one breaker on each bus is dedicated to
this function, leaving 20 breakers for each bus for secondary distribution.
Supplementary power distribution shelf (optional)
A supplementary power distribution shelf can be configured. See
Distribution Shelf" (page
Power cable junction box
The power cable junction box provides connection for supplementary
shelves and is standard equipment on the CPDC.
500W inverter (optional)
The 500W inverter is an optional component that serves convenience
outlets located in the equipment lineup endguards. The inverter kit contains
the A0367433 LaMarch inverter, which converts the -48 V (nominal) DC
from the office battery to 110 V AC.
Bulkhead filler panel
Two bulkhead filler panels are used when the CPDC is in a lineup without
a SuperNode, Link Peripheral Processor (LPP), or ENET mounted in a
cabinet.
16-inch filler panel
One 16-in. (0.41 m) filler panel comes standard with the CPDC and is
mounted at shelf position 14. One or two other panels should be used to fill
unused PDS shelf spaces at positions 30 and 46.
Refer to
Copyright © 2006, Nortel Networks
.
Maintenance and administration cabinet modules 133
132).
Figure 62 "CPDC components" (page 134)
Communication Server 2100
Meridian SL-100 Product Guide
555-4001-103 20.01 Standard
SE09 20 October 2006
"Power
for CPDC components.