Chapter 3 Digital Keypad Operation and Start Up|

3.2.2 Explanations for the Tuning Steps

3.3.2.1 Step 1

Basic parameters settings for the motor
Make sure that Pr.00-00 (identity code of the AC motor drive) corresponds with the
nameplate indicated on the AC motor drive.
Make sure that all parameters are reset to factory setting (Pr.00-02 is set to 9 or 10).
Pr.00-02
Parameter Reset
Enter the related information of the motor into Pr.01-00~01-02 and Pr.05-01~05-04
Pr.01-00
Max. Output Frequency
Pr.01-01
1st Output Frequency
Setting 1
Pr.01-02
1st Output Voltage
Setting 1
Pr.05-01
Full-load Current of
Motor 1 (A)
NOTE: This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. The factory setting is 90% of the rated current.
Pr.05-02
Rated Power of Motor 1
(kW)
NOTE: It is used to set rated power of the motor 1. The factory setting is the power of the drive.
3-10
CALL NOW 800-985-6929
0: No function
1: Read only
2: Enable group 11 parameters setting
8: Keypad lock
9: All parameters are reset to factory settings (50Hz,
220V/380V)
10: All parameters are reset to factory settings (60Hz,
220V/440V)
50.00 ~ 600.00Hz
0.00~600.00Hz
230V: 0.1V~255.0V
460V: 0.1V~510.0V
40~120% of drive's rated current
0~655.35
CALL NOW 800-985-6929
http://www.automatedpt.com
Revision Dec. 2008, 04VE, SW V2.05