B.5 Zero Phase Reactor (Rf220X00A) - Delta Electronics VFD-VE User Manual

High performance field oriented control ac motor drives
Table of Contents

Advertisement

B.5 Zero Phase Reactor (RF220X00A)

Dimensions are in millimeter and (inch)
Recommended Wire
Cable
Size
type
(Note)
2
AWG mm
≦10 ≦5.3
Single-
core
≦2 ≦33.6
≦12 ≦3.3
Three-
core
≦1 ≦42.4
Note: 600V Insulated unshielded Cable.
Diagram A
Please wind each wire 4 times around the
core. The reactor must be put at inverter
output as close as possible.
R/L1
U/T1
Power
S/L2
V/T2
Supply
T/L3
W/T3
Revision Dec. 2008, 04VE, SW V2.05
CALL NOW 800-985-6929
Wiring
Qty.
Method
Nominal
2
(mm
)
Diagram
1
≦5.5
A
Diagram
4
≦38
B
Diagram
≦3.5
1
A
Diagram
4
≦50
B
Zero Phase Reactor
MOTOR
CALL NOW 800-985-6929
http://www.automatedpt.com
Appendix B Accessories|
Diagram B
Please put all wires through 4 cores in
series without winding.
Zero Phase Reactor
Power
R/L1
U/T1
S/L2
V/T2
Supply
T/L3
W/T3
Note 1: The table above gives approximate
wire size for the zero phase reactors but the
selection is ultimately governed by the type
and diameter of cable fitted i.e. the cable
must fit through the center hole of zero
phase reactors.
Note 2: Only the phase conductors should
pass through, not the earth core or screen.
Note 3: When long motor output cables are
used an output zero phase reactor may be
required to reduce radiated emissions from
the cable.
http://www.automatedpt.com
MOTOR
B-15

Advertisement

Table of Contents
loading

Table of Contents