11.32
Trip-Circuit Supervision
Setting Values
Number of monitored circuits per circuit-breaker function group
Operating mode per circuit
Pickup and dropout time
Adjustable indication delay with 1 binary input
Adjustable indication delay with 2 binary inputs
SIPROTEC 5, Low-Impedance Busbar Protection 7SS85, Manual
C53000-G5040-C019-6, Edition 06.2016
11.32 Trip-Circuit Supervision
1 to 3
With 1 binary input
With 2 binary inputs
Approx. 1 s to 2 s
1.00 s to 600.00 s
Increments of 0.01 s
1.00 s to 30.00 s
Increments of 0.01 s
Technical Data
613