E2-03 No Load Current
Setting Range:
Model Dependent (see Appendix B)
Factory Default: Model Dependent
Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper value
if the no load current is not stated on the motor nameplate.
E2-05 Motor Line-to-Line Resistance
0.0000 to 65.000 Ω
Setting Range:
Factory Default: 9.842 Ω
Sets the line-to-line resistance of the motor's stator winding. Usually determined by performing Auto-tuning. If Auto-tuning
cannot be completed without error, then manually set E2-05 to the value as determined by the motor manufacturer. Remember
this value must be entered as line-line and not line neutral.
(
Phase-to-phase Resistance at
E2-05=
Insulation Class Temperature
F6 Com OPT Setup (applies only to the LonWorks option)
F6-01 Operation Selection After Communication Error
Setting
0
Ramp to Stop
1
Coast to Stop (factory default)
2
Fast-Stop
3
Alarm Only
If a serial communication option board is attached to the Drive at the 2CN connector, the Drive will automatically monitor the
card for any type of communication errors. F6-01 is applicable no matter whether a run command or speed command is coming
via the option board, digital operator, or terminal input. The setting of F6-01 determines whether the communication error is
seen as a fault or an alarm. If F6-01= "3: Alarm Only", then the fault output is not energized upon a communication error. All
other settings of F6-01 cause the fault output to energize. The setting of F6-01 does not apply to any of the embedded
communication protocols used at the RS-485/422 terminals on the removable terminal board. (See parameters H5-0X).
F6-02 Option PCB External Fault Detection Selection
Setting
0
Always Detected (factory default)
1
Detected only during operation
)
273 + (25 + insulation class temperature) /2
X
Description
Description
Programming 44
273 + insulation class temperature
Where: Insulation class temperature is in °C