STAGE DELAY TIMER
Default ON. When ON, all stage delay timers
(stages 2, 3, and 4) are enabled and will serve to
bring on additional stage(s) of cooling or heating
on a timed basis (default 20 minutes) in cases
when the previous stage of heating or cooling will
not raise or lower the room temperature to the set
point in a given time.
When OFF is selected all stage delay timers are
disabled. This means stages are changed based
on the temperature and not their timer delays.
Scroll to STG DELAY TIMERS; and touch to
select the applicable stage delay timer. Touch < to
return to previous menu.
STAGE DELAY DIFFERENTIALS
Stage delays and differentials are individual set in
the installer settings screen.
STAGE 1 DIFF
Stage 1 differential is used in all thermostats. The
default is 1.0°F but can be programmed between
0.5° and 8.0°F in 0.5°F increments. Touch < to
return to previous menu.
STAGE 2 THROUGH 4 DIFF
(Where applicable) The default is 1.0°F but can be
programmed between 0.5° and 8.0°F in 0.5°F
increments. Touch < to return to previous menu.
STAGE 2 THROUGH 4 DELAYS
(Where applicable) If STG DELAY TIMERS is
turned ON, the default delay is 20 minutes but can
be programmed from 5 to 120 minutes in 5-minute
increments. If first stage fails to advance the
ambient temperature toward the setpoint by 1.0°F
in the programmed delay time, then the second
stage is activated.
Scroll to STG 2 DELAY (or 3 or 4); touch to select.
Select the desired delay. Touch < to return to
previous menu.
H/C STAGES LOCKED IN
When disabled the heat/cool stages are turned off
separately). When enabled (default), heat/cool
stages are turned off together. Touch < to return to
previous menu.