9 Auxiliary Settings
[Notes on system confi guration check]
Never perform a system confi guration check unless you have actually changed the
system confi guration.
System confi guration changes include addition, moving, and removal of units, and
address change.
Never perform a system confi guration check when a power outage occurs on the air
conditioner side or when temporary communication failure is generated.
If a system confi guration registration is performed in such situations, the air conditioners
that should be recognized may not be recognized.
If "System confi guration change!" is displayed as a result of your accidentally performing
a system confi guration check, never proceed to the current system confi guration
registration process. First take correction measures against the causal erroneous status,
then click on "NO" .
If the system confi guration is confi rmed to be as it originally was, "No confi guration
change" will be displayed.
Note that if you leave the screen with the message "System confi guration change!"
displayed for 1 hour or more, the current system confi guration confi rmation process will
be automatically performed and registered.
(2) Initialization
If you click on the "Initialization" button, the message shown below will be displayed:
If you click on "YES" , system confi guration data and setting data will be deleted.
All alarm logs and alarm e-mail delivery logs will be also deleted.
The following data will not be deleted:
Network settings ("WEB settings" screen)
IP addresses, subnet mask, default gateway, DNS, WINS, and device name
All user settings ("User settings" screen)
(3) If you attempt to log in using a special/general user account while the Web Interface is in
the process of a system confi guration check, current system confi guration registration,
or initialization, the message shown below will be displayed, and you cannot log in. Wait
then try to log in again.
(The administrator user can log in, but Web operations will not be available. The above
message will be displayed) The same message will be also displayed when an already
logged in user attempts to perform any operation while the Web Interface is in the process
of the above procedures.
43
Main
Do not make
!!
imprudent
initialization.