DESCRIPTION OF THE BOILER 1. 1 INTRODUCTION They comply with the european directives combustion chamber with electronic igni- 90/396/CEE, 89/336/CEE, 73/23/CEE, tion and control. “PLANET DEWY 90 A - 110 A” boilers are 92/42/CEE and with the european specifi- premix condensation thermal appliances cation EN 483.
INSTALLATION The boiler must be installed in a fixed loca- tion and only by specialized and qualified firms in compliance with all instructions contained in this manual. Furthermore, the installation must be in accordance with cur- rent standards and regulations. 2.
Page 8
installed (excluding the doublers) and must not be greater than 12.5 mm H (version “90 A”) e 15.5 mm H O (version 1a-b Coaxial duct kit code 8096200 “110 A”). For head losses in the fittings, Extension L. 1000 code 8096100 refer to Table 2.
Page 9
TABLE 2 Accessories ø 80 Head loss (mm H O) vers. “90 A” Head loss (mm H O) vers. “110 A” Inlet Outlet Roof outlet Inlet Outlet Roof outlet 90° elbow MF 0,30 0,40 – 0,30 0,50 – 45° elbow MF 0,20 0,30 –...
Page 10
ø 60 PIPING SYSTEM A special kit for separating smoke release Separate pipes kit code 8089903 pipes and air intake pipes. 90° elbow MF code 8077404 The diameter 80 intake pipe may be installed 90° elbow MF with take-off points code 8077407 to the right or left of the diameter 60 smoke 4 a Extension L.
Page 11
2.7. 1 Accessories ELECTRICAL CONNECTION 2.8. 1 Room stat connection completing installation The boiler is supplied with an electric cable. To gain access to the TA-CR-SE (J2) elec- Should this require replacement, it must be tronic board connector, remove the control The complete range of accessories requi- purchased exclusively from SIME.
Page 12
periods per day, individually selectable. – Copy function for easy transfer of heating programme to the next or previous day. – Holiday programme: the programme is interrupted for the holiday period and automatically restarted on returning home. – Option to return the heating program to default values.
Page 13
HEATING CIRCUIT SETTINGS Antifreeze protection Heating takes place up to this pre-set value if the plant is activated in stand- "Pre-set ambient by (e.g. holidays). temperature value" In this way, the building antifreeze function is active, preventing an excessive lowering of the ambient. Summer/Winter switch-over This parameter regulates the temperature of the automatic summer/win- temperature...
Page 14
SERVICE VALUES This block (1) can be activated to display all the parameters without modify- Final user level 2 ing them. Pressing buttons displays “OFF”. programming block WARNING: The activation block can be deactivated temporarily by pressing buttons simultaneously; a confirmation sign appears on the display. At this point press simultaneously the buttons for at least 5 sec- onds.
CHARACTERISTICS 3. 1 ELECTRONIC BOARD 3. 1 .2 D.H.W. operation ignition (STEP), of the gas valve. According to the type of gas for which the The electronic boards are manufactured in Upon demand for hot water, the boiler boiler is equipped, the trimmer must be compliance with the EEC 73/23 low-voltage starts instantaneously...
Page 17
A flow switch safety valve intervenes, block- ing the operation of the burner if the boiler is without water due to the formation of an air lock in the heat exchanger or if the cir- culator is not working. with boiler by-pass con by-pass NOTE: If replacing the flow switch valve, without boiler by-pass...
USE AND MAINTENANCE THE BENCHMARK INITIATIVE All relevant sections of the logbook must be filled in at the time of installation and there- after service information on the back page of the logbook. Commissioning of the boiler is not complete until the logbook is filled in.
Page 19
4.4.2 Diagram illustrating heat output in relation to “air ∆p” version “110 A” EXPANSION VESSEL To disassemble the expansion vessel, pro- ceed as follows: – Make sure that the water has been emp- tied out of the boiler. – Unscrew the connection and the locknut. –...
FAULT FINDING If an electrical fault occurs on the appliance SHORT CIRCUIT approx.: 240 V ac. the preliminary electrical system checks CHECK – Test leads from L to E “ ” meter reads contained in the British Gas Multimeter approx. 240 V ac. Instruction Booklet must be carried out Switches turned FULL ON - meter set on Ω...
Page 21
C.H. MODE - FAULT FINDING Start from cold Rotary switch set to WINTER position. Room thermostat (if fitted) calling for heat and all D.H.W. taps off. C.H. thermostat set to maximum position. Clock in the on position (if fitted). Is there power Make Does Turn the clock...
Page 22
D.H.W. MODE - FAULT FINDING Start from cold - rotary switch set to SUMMER position, D.H.W. thermostat set to maximum, and all D.H.W. taps OFF. Is there power Make Does Does the boiler at the external power the fan remain in socket? available start?
STANDARD SETTINGS OF THE “LOGICA REMOTE CONTROL” C.H. WITHOUT ZONE MULTI-ZONE C.H. WITH EXTERNAL WITHOUT EXTERNAL WITH EXTERNAL WITHOUT EXTERNAL TEMPERAT. SENSOR TEMPERAT. SENSOR TEMPERAT. SENSOR TEMPERAT. SENSOR Function Value Function Value Function Value Function Value 20 - 25°C – –...